Technical Specification
Parameter
Smoke Alarm
Heat detector
Operating modes
Indicators
Volume of the warning
Sound frequency
Power Supply
Standby power consum.
Alarm power consum.
Battery life
Low battery threshold
In event of low battery
Operating temperature
Humidity during operation
Color
Dimensions (D x H)
Weight
Supervision monitoring
Wireless trans. Power
Wireless range
Standards Compliance
Description
Photoelectrical chamber with optical sensor for
detecting smoke
4 sensors for measuring temperature increase,
alarm will be triggered at 60°C
Smoke + Heat (OR Logic), Only Smoke, Only Heat
Audible (Piezo) and visual (LED)
Min. 85 dB at 3m (10')
3.25 kHz
CR123A 3V x 4
0.02mA (typical)
100mA
4 years (typical)
2.65 V
One beep every 30 seconds
0°C to 55°C
10% to 85% RH, no condensation or icing
White
Ø 133.8 x 50.2 mm (Ø 5.27 x 1.98')
360 g (net)
1-255 min. (user defined)
10mW
Up to 300m (unobstructed)
EN14604:2005/AC:2008. 1134-CPR-186
NOTE: Only the "Smoke Operation Mode" is
approved to EN14604.
11