Output setup parameters
Parameter
Index
Name
Hex(Dec)
Setpoint BDC1
Setpoint 1
0x3C(60)
Setpoint 2
Switchpoint BDC1
Logic
Mode
0x3D(61)
Hysteresis
Setpoint BDC2
Setpoint 1
0x3E(62)
Setpoint 2
Switchpoint BDC2
Logic
0x3F(63)
Mode
Hysteresis
SIO Channel 1
Stage Mode
Source
Timer Mode
0x40(64)
Timer Scale
Delay Duration
Divider
NO/NC
Operation
Subindex
Access
Default value
Hex(Dec)
0x01(1)
R/W
0x02(2)
R/W
0x01(1)
R/W
0x02(2)
R/W
0x03(3)
R/W
0x01(1)
R/W
0x02(2)
R/W
0x01(1)
R/W
0x02(2)
R/W
0x03(3)
R/W
0x01(1)
R/W
0x02(2)
R/W
0x03(3)
R/W
0x04(4)
R/W
0x05(5)
R/W
0x06(6)
R/W
0x08(8)
R/W
Rev. 00 | IBS04, ICS05, ICS08, ICB12, ICB18, ICB30 Sensores inductivos con interfaz IO-Link | © 2018 | CARLO GAVAZZI Automation
Data range
0 = 62 % sensing range(IBS, ICS05)
0 = 50 % sensing range (ICS08)
1
1 = 100 % sensing range
0 = 62 % sensing range(IBS, ICS05)
0
0 = 50 % sensing range (ICS08)
1 = 100 % sensing range
0 = Normal operation BDC1
0
1 = Inverted operation BDC1
0 = Deactivated
1 = Single point mode
1
2= Window mode
3 = Two point mode
0 = Standard hysteresis ≈ 10%
0
1 = Extended hysteresis ≈ 20%
100
1 to 7000 Hz
50
1 to 7000 Hz
0 = Normal operation BDC2
0
1 = Inverted operation BDC2
0 = Deactivated
1 = Single point mode
1
2= Window mode
3 = Two point mode
10
1 to 7000 Hz
0 = disabled output
1 = PNP output
1
2 = NPN output
3 = Push-pull output
1 = BDC1
1
2 = BDC2
5 = Temperature Alarm
0 = disabled
1 = T-ON delay
2 = T-OFF delay
0
3 = T-ON & T-OFF delay
4 = One-shot leading edge
5 = One-shot trailing edge
0 = Milliseconds
0
1 = Seconds
2 = Minutes
100
1 to 32767
1
1 to 32767
0 = Normally Open
0
1 = Normally Closed
Data Type
(Length)
IntegerT16
IntegerT16
UIntegerT8
UIntegerT8
IntegerT16
IntegerT16
IntegerT16
UIntegerT8
UIntegerT8
IntegerT16
UIntegerT8
UIntegerT8
UIntegerT8
UIntegerT8
IntegerT16
IntegerT16
UIntegerT8
21