ISO524-1
INSTALLATION INSTRUCTIONS
FOR PACKAGED ISOLATOR
Figure 2a: Yellow Wire Not Used
ISO524-1
Red
Red
Device
Black
TO NEXT DEVICES
Device
Yellow
Red
Red
ISO524-1
DOP-IOD006
EN54-17: 2005
GENERAL DESCRIPTION
The System Sensor ISO524-1 short circuit isolator is designed for use
with all 200 and 500 series analogue addressable detectors and modules.
They prevent an entire communications loop from being disabled when a
short circuit occurs. They accomplish this by isolating that part of the loop
containing the short from the remainder of the circuit. These isolators
also automatically restore the entire loop when the cause of the short
circuit is corrected. The isolator has been designed such that if the short
circuit occurs between adjacent ISO524-1 and / or B524IEFTx units, and
no other products are connected between, the operation of the entire
loop will remain intact in the event of this one short circuit, dependent on
control panel operation.
SPECIFICATIONS
Length:
Width:
Height:
Flying Lead Length:
Flying Lead Cable:
Operating Temperature Range: -30°C to 70°C
( + )
Operating Humidity Range:
Operating Voltage:
Standby Ratings:
( - )
Isolation Current
Maximum rated continuous current with the isolator closed (I
Maximum rated isolator current (under short circuit) (I
Max. leakage current (I
Max. series impedance with the isolator closed (Z
Line impedance per base
WARNING - Do not use high voltage continuity tester units, such as
meggers, with isolator modules connected.
( - )
MOUNTING
The ISO524-1 Isolator may be installed in various convenient locations,
such as junction boxes, behind sensor bases, within callpoint back-
boxes, or within SMB500 module boxes.
INSTALLATION GUIDELINES
( + )
All wiring must be installed in compliance with all applicable local codes
and any special requirements of the local authority having jurisdiction,
using the proper wire sizes. The conductors used to connect smoke
detectors to control panels and accessory devices should be colour-
coded to reduce the likelihood of wiring errors. Improper connections can
prevent a system from responding properly in the event of a fire.
For signal wiring (the wiring between interconnected detectors), it
is recommended that the wire be no smaller than 0.5 mm
wire sizes up to 2.5 mm
cable connectors. The use of twisted pair wiring or shielded cable for the
power (+ and -) loop is recommended to minimize the effects of electrical
interference.
If shielded cable is used, the shield connection to and from the isolator
must be continuous by using wire nuts, crimping, or soldering, as
appropriate, for a reliable connection.
Alarm system control panels have specifications for allowable loop
resistance. Consult the control panel specifications for the total loop
resistance allowed before wiring the detector loops.
1. Using suitable cable connectors, connect the incoming and outgoing
loop positive cables to each of the two available Red ISO524-1 cables.
2. Connect the Yellow cable to Device +ve, in order to maintain device
+ve irrespective of the position of the short circuit (Fig 2b), otherwise
do not connect (Fig 2a).
3. Connect the incoming and outgoing loop negative cables to the single
Black ISO524-1 cable .
4. Check the entire loop wiring before applying power. This includes
checking the wiring for continuity, correct polarity and ground fault
testing.
5. Once all loop cabling has been checked, power may be applied to the
system and functional tests carried out.
1
Pittway Tecnologica S.r.l., Via Caboto 19/3, 34147 Trieste, Italy
I 56- 1642- 016
E N G L I S H
90mm max.
37mm max.
10mm max.
120mm
Multi-strand 0.75mm²
0% to 95% Relative Humidity
(Non-condensing)
15 to 28.5 VDC
100µA @ 24 VDC
8µA @ 6 VDC
15mA at 24VDC
max) with the isolator open (isolated state): 15mA
L
max): 170 m ohm at
c
15Vdc
0.2 ohms max. @ 24 VDC
can be used with the isolator, using suitable
2
max): 1A
c
max): 1A
s
. However,
2
I56-1642-016

Publicidad

loading

Resumen de contenidos para System Sensor ISO524-1

  • Página 1 CH-1180 ROLLE, Switzerland 1. Using suitable cable connectors, connect the incoming and outgoing loop positive cables to each of the two available Red ISO524-1 cables. 2. Connect the Yellow cable to Device +ve, in order to maintain device +ve irrespective of the position of the short circuit (Fig 2b), otherwise do not connect (Fig 2a).
  • Página 2 2. Collegare il cavo Giallo a Device +ve per mantenere +ve non legata alla posizione del corto circuito (Fig 2b), altrimenti non collegare (Fig 2b). 3. Collegare entrambe i cavi della linea negativi al cavo Nero dell'ISO524-1. 4. Prima di applicare l’alimentazione, controllare l’intero cablaggio del loop.
  • Página 3 Figura 2b: Cable amarillo utilizado MONTAJE El aislador ISO524-1, gracias a su reducido tamaño, se puede instalar en el interior de cajas de conexiones, debajo de las bases de los sensores, dentro ( - ) ( - ) de las cajas de pulsadores, o bien dentro de las cajas de módulos SMB500...
  • Página 4 D E U T S C H ANLEITUNG FÜR DEN EINBAU VON KOMPAKTEN ISOLATOREN ALLGEMEINE BESCHREIBUNG Der Kurzschluß-Isolator ISO524-1 von System Sensor ist für den Einsatz bei allen Meldern und Modulen der Serien 200 und 500 geeignet. Er verhindert, daß ein Abbildung 1: Aussehen kompletter Loop beim Auftreten eines Kurzschlusses ausfällt.