WattStation™ Wall Mount User Manual
1. Grounding Instructions
1.1 Safety and Compliance
Read all instructions before using this product.
Do not use this product if the flexible power cord or charging cable are frayed, have broken insulation, or
any other signs of damage.
Do not use this product if the enclosure or the charging connector is broken, cracked, open, or show any
other indication of damage.
This document provides instructions for the wall mounted WattStation and should not be used for any
other product. Before installing WattStation you should review this manual carefully and consult with a
licensed contractor, licensed electrician, or trained installation expert to ensure compliance with local
building codes, climate conditions, safety standards and state and local electrical codes.
1.2 Grounding Instructions
WattStation must be connected to a centrally grounded electrical system. Ground conductors entering
WattStation must be connected to the equipment grounding bar inside the charger. Connections to
WattStation shall comply with all applicable electrical codes and ordinances.
2. Installation Instructions
2.1 Installation Tools and Requirements
Recommended Tools:
Slotted screwdriver (3/16" or
•
Electric drill
•
Wire stripper
•
Wall mounting hardware (refer to section 2.2.1 or section 2.3.1)
•
Phillip's head screwdriver
•
Water-tight conduit hub (hardwired version only)
•
2.2 Plug-in Version
2.2.1 Before Installation
WattStation should be installed only by a licensed contractor, and/or a licensed electrician in
accordance with all applicable state, local and national electrical codes and standards.
Ensure that a dedicated circuit, capable of supplying 30A at 208-240 VAC, is available
•
Power feed must have a centrally grounded neutral in order for WattStation to function correctly.
•
Wall receptacle must be a NEMA 6-50 outlet. A recommended 40A upstream circuit breaker,
•
located either in a panelboard or load center, should be used
Distance between the wall power receptacle and WattStation mounting should be less than one
•
(1) foot
Wall power receptacle with a weatherproof locking cover is required
•
3
")
GE Energy
©2012 GE Company All Rights Reserved