CONNECTIONS
DRAIN PIPE CONNECTION
The indoor unit is fitted with a condensate drain pipe to
which a lagged drainage hose should be connected leading
to a suitable drainage outlet. The appliance is designed for
condensate drainage from either side, although the drain
pipe is connected in the factory on the left.
- Remove front panel as described in Maintenence section.
- Using a tool remove fixing spring located in left condesate
pipe.
- Remove plug present.
- Place fixing spring in right condensate pipe.
- Replace front panel
Connect a lagged drainage pipe (inside ø 16 mm) to the
hose fitting of the drain pipe and direct it towards a suit-
able drainage outlet.
After installation, check that the condensation flows out
regularly.
For data regarding installation, see the section "Informa-
tion for installation".
To access the connections, see the section "Access to
connections".
The drainage pipe must have a 3% slope downwards
towards the drain.
Check all the joints for leaks.
Apply heat-insulating material to the joints.
CONNECTION TO THE WATER SYSTEM
For connections at the sides:
- Remove the relevant knockout from the housing
For connections at the rear:
- Drill a hole Ø 60 in the wall within one of the two areas A"
(see section "Information for installation").
Pass a protective plastic pipe through the hole in the
wall.
Ensure that the section of wall in question has no bear-
ing structural members, pipes or electric cables.
Upon completion of work it is advisable to close the
holes made in the wall using elastic and, if possible,
soundproofing material.
- To facilitate carrying out the water connections, keep the
unit raised by means of a spacer.
- If necessary position the connections in the space provid-
ed at the rear of the indoor unit and fix them with the pro-
vided bracket A.
Position the pipes so that they occupy as little space as
possible in order to facilitate hooking of the appliance
onto the metal plate.
10
GB
Knockouts
Indoors
A
Protective pipe
Installer
Outdoors
2~5 mm