Design and function
5.2
Stroke limiter
In versions with the stroke limiter, stroke limiting is set to 90° ex works. This setting can be
changed if required. This allows the turning movement towards working position to be limited
to less than 90°, e.g. 45°.
NOTE
In versions with the DA function, limiting is possible only towards the open position.
1
Covering cap
2
Adjusting screw
3
Locknut
5.2.1 Adjusting the stroke limiter
Check that there is no compressed air present
Unscrew the cover (1)
Use the control air to bring the actuator to working position
(DA function: CLOSED position)
Loosen the locknut (3)
Turn the adjusting screw (2) counter-clockwise (FC function) or clockwise (FO/DA function)
to obtain the desired stroke limitation
Actuator in rest position (DA function: OPEN position)
Test the stroke limiter. Repeat steps 3 to 6 if necessary
Tighten the locknut (3).
Screw on the covering cap (1)
34