INSTALLATION MANUAL Galvanic Isolator VDI-16
1. Mounting location
Warning!
For safety purposes, the product should be installed in a heat-resistant environment. Avoid the presence of e.g. chemicals,
synthetic components, curtains or other textiles in the immediate vicinity of the product.
1.1. Install the galvanic isolator in a well ventilated area.
1.2. Keep a clear space of 10 cm around the product for ventilation.
1.3. The galvanic isolator must be mounted with its length vertical to allow for maximum cooling. Under normal circumstances, the
temperature increase of the heat sink is not more than 20° C. However the unit may become hot when conducting fault ground
current.
2. Installation
Warning!
The galvanic isolator must be wired into the green (safety) grounding conducting connection ahead of all grounding connections
to the vessel such that no ground connections on the vessel bypass the galvanic isolator making it ineffective.
2.1. Connections and safety features must be according to the locally applicable regulations.
2.2. Use electric cables of the appropriate size.
2.3. Wire the galvanic Isolator into the green (safety) grounding conducting connection as shown in fig. 1.
Figure 1: wiring diagram
INSTALLATIE MANUAL Galvanische Isolator VDI-16
1. Locatie
Waarschuwing!
Dit product dient in een hittebestendige omgeving geïnstalleerd worden. Voorkom daarom de aanwezigheid van bijvoorbeeld
chemicaliën, kunststof onderdelen, gordijnen of ander textiel, etc. in de directe omgeving.
1.1. Installeer dit product in een droge, goed geventileerde ruimte.
1.2. Rondom het apparaat dient een ruimte van tenminste 10 cm te worden vrijgehouden voor koeling.
1.3. De galvanische isolator moet t. b. v. optimale koeling verticaal gemonteerd worden. Onder normale omstandigheden zal het
koellichaam niet meer dan 20° C warmer worden t. o. v. de omgeving. In geval van kortsluitstromen kan het apparaat heet
worden.
2. Installatie
Waarschuwing!
De galvanische isolator dient in de groen/gele aardraad verbinding gemonteerd te worden, vóór de aardverbinding naar het
schip.
2.1. Aansluitingen en beveiligingen moeten in overeenstemming met de plaatselijk geldende voorschriften worden uitgevoerd.
2.2. Gebruik kabel met de juiste aderdoorsnee.
2.3. Monteer de galvanische isolator in de groen/gele aardraad verbinding zoals aangegeven in fig. 1.
Figuur 1: Aansluit schema
Phone: (+31) (0)36 535 97 00 │ Fax: (+31) (0)36 535 97 40 │ www.victronenergy.com │ e-mail: sales@victronenergy.com
Victron Energy B.V. │ De Paal 35 │ 1351 JG ALMERE │ The Netherlands
Galvanic Isolator VDI-16
Waterproof (potted)
Maximum current
Peak current
Connection
Heat sink
Material
Protection category
Weight
Dimensions (hxwxd)
Galvanische Isolator VDI-16
Netaansluiting tot
Piekstroom
Aansluiting
BEHUIZING
Materiaal
Beschermklasse
Gewicht
Afmetingen (hxbxd)
EN
16 A
1600 A / 20 ms
2 studs M6
Anodized aluminium
IP 67
1 kg
60 x 120 x 200 mm
NL
Volledig waterdicht:
in epoxyhars gegoten
tot 16 A
1600 A / 20 ms
2 bouten M6
(messing vernikkeld)
Geanodiseerd
aluminium
IP 67
1 kg
60 x 120 x 200 mm

Publicidad

loading

Resumen de contenidos para Victron energy VDI-16

  • Página 1 Afmetingen (hxbxd) 60 x 120 x 200 mm Victron Energy B.V. │ De Paal 35 │ 1351 JG ALMERE │ The Netherlands Phone: (+31) (0)36 535 97 00 │ Fax: (+31) (0)36 535 97 40 │ www.victronenergy.com │ e-mail: sales@victronenergy.com...
  • Página 2 2.2. Utiliser des câbles électriques de la taille appropriée. 2.3. Brancher l’isolateur galvanique sur la connexion circulant par la terre en vert (sécurité) comme il est montré sur le schéma 1. Isolateur Galvanique VDI-16 Résistant à l’eau (en pot) Courant maximum 16 A Intensité...
  • Página 3 60 x 120 x 200 mm Figura 1: diagrama de cableado Victron Energy B.V. │ De Paal 35 │ 1351 JG ALMERE │ The Netherlands Phone: (+31) (0)36 535 97 00 │ Fax: (+31) (0)36 535 97 40 │ www.victronenergy.com │ e-mail: sales@victronenergy.com...