No: 24567 – 04/20 rev. 2
Catalog Numbers • Les Numéros de Catalogue • Números de Catálogo: BZ-200/BZ-250/BZ-250-347
Country of Origin: Made in China • Pays d'origine: Fabriqué en Chine • País de origen: Hecho en China
Models ending in -U are BAA and TAA compliant (Product produced in the U.S.)
Auto/Manual Mode Switch
BZ-250, BZ-250-347 only
Sélecteur de mode Auto/
Manuel BZ-250, BZ-250-347
uniquement
Interruptor deslizante de
encendido automático/manual
BZ -250/ BZ- 250-347
solamente
DESCRIPTION AND OPERATION
The BZ-2xx series of power packs are the foundation for any low
voltage lighting control system. The BZ-2xx series supplies low
voltage power to occupancy sensors and other control devices,
switching line voltage in response to signals from control devices.
The BZ-2xx series of power packs attaches to existing junction
boxes or mounts into fixture wiring trays.
Low voltage wiring should use at least 22-gauge wire. High voltage
connections should be appropriately sized for the breaker and load.
Always check local building codes. After initial wiring is complete,
check wiring diagrams to verify the power pack is wired correctly.
Improper wiring can cause damage to the power pack, lighting
system, occupancy sensors, and other control devices.
INSTALLATION
Installation Notes
1. * Refer to occupancy sensor data sheet to determine
maximum number of sensors. Power pack mA output is
225mA.
2. Power packs should be installed in accordance with state,
local and national electrical codes and requirements.
3. Power packs are designed to attach to existing or new
electrical enclosures with 1/2 inch knockouts.
4. Most applications require UL listed, 18-22 AWG, 3-conductor,
Class 2 cable for low voltage wiring. For plenum return
ceilings, use UL listed plenum-approved cables.
5. The BZ-2xx is a Class 2 Output Power Supply, suitable for
parallel interconnection of up to 4 units maximum. This power
pack is UL Listed for Interconnection of Power Sources in
accordance with National Electric Code.
NOTE: The BZ series uses an AC power relay and is not
typically suited for high-impedance DC or dry-contact
applications.
Wattstopper
Power Pack
Bloc d'alimentation
Fuente de Energia
Installation Instructions • Instructions d'Installation • Instrucciones de Instalación
SPECIFICATIONS
Voltages
BZ-200, BZ-250 ................120—277 VAC, 50/60 Hz, single phase
BZ-250-347 ......................120—347 VAC, 50/60 Hz, single phase
Load Requirements
Ballast/ELV/MLV/Incandescent/LED
BZ-200, BZ-250......................................20 A @ 120—277 VAC
BZ-250-347 ............................................16 A @ 120—347 VAC
E-Ballast/CFL .............................................16 A @ 120—277 VAC
Motor
BZ-200, BZ-250 .................................... 1 HP @ 120—240 VAC
BZ-250-347 ......................................... 1/4 HP @120—347 VAC
Plug Load
(BZ-200, BZ-250) ............................................20 A @ 120 VAC
(BZ-250-347) ...................................................15 A @ 120 VAC
Class 2 Output
BZ-200 (w/relay connected) ........................225 mA @ 24 VDC
BZ-250, BZ-250-347 ....................................225 mA @ 24 VDC
Low Voltage Input, Control ON ............................................ 5—30 VDC
Operating Temperature .................................. -4°—131 °F (-20—55 °C)
Storage Temperature .................................... -40°—176 °F (-40—80 °C)
UL/C-UL Listed
Connect wires as shown in the following wiring diagrams, or as
shown in the BI-LEVEL CONTROL section.
WARNING: TURN THE POWER OFF AT THE
CIRCUIT BREAKER BEFORE WIRING.
White
Neutral
BZ-200
Black
Hot
Power Pack
**Ground
** BZ-200 Power Pack
must be grounded to
ensure signal integrity,
not for safety ground.
Wiring for one BZ-200
®
WIRING
Optional
Local Off
Switch
Red
Red
Low Voltage Wires
Control Output
Any
24VDC
Common
Ceiling/Wall
Sensor
+24VDC
Fixture
*To
Additional
Sensor(s)