Lock: indicates that the UPS or one of its components has been locked and is normally preceded by an alarm
¾
signal. In the event of a fault with and consequent lock of the inverter, it will switch off and the load will be
powered by the bypass line (this procedure is excluded for locks due to serious, persistent overloads and short
circuits).
CODE
L01
L02
L03
L04
L05
L06
L07
L08
L09
L10
L11
L12
L13
L14
L15
L16
L17
L18
L19
L20
L21
L22
L23
L24
L25
L26
L27
L28
L29
L30
L31
L34
L35
L36
L37
L38
L39
L40
L41
L42
L43
L44
IV333 Rev.000 SIEL S.p.A.
Data di emissione: 2011-09-28
Incorrect auxiliary power supply
Disconnection of one or more internal cables
Input fuse of Phase 1 blown or input static switch faulty (does not close)
Input fuse of Phase 2 blown or input static switch faulty (does not close)
Input fuse of Phase 3 blown or input static switch faulty (does not close)
Positive stage BOOST overvoltage
Negative stage BOOST overvoltage
Positive stage BOOST undervoltage
Negative stage BOOST undervoltage
Fault bypass static switch
Phase 1 inverter overvoltage
Phase 2 inverter overvoltage
Phase 3 inverter overvoltage
Phase 1 inverter undervoltage
Phase 2 inverter undervoltage
Phase 3 inverter undervoltage 3
Direct voltage at inverter output or distorted Phase 1 inverter sine wave
Direct voltage at inverter output or distorted Phase 2 inverter sine wave
Direct voltage at inverter output or distorted Phase 3 inverter sine wave
Overload on Phase 1 output
Overload on Phase 2 output
Overload on Phase 3 output
Short circuit on Phase 1 output
Short circuit on Phase 2 output
Short circuit on Phase 3 output
Output fuse of Phase 1 blown or output remote control switch locked (does not close)
Output fuse of Phase 2 blown or output remote control switch locked (does not close)
Output fuse of Phase 3 blown or output remote control switch locked (does not close)
Phase 1 heat sink overtemperature
Phase 2 heat sink overtemperature
Phase 3 heat sink overtemperature
Battery charger overtemperature
Faulty Phase 1 heat sink temperature sensor
Faulty Phase 1 heat sink temperature sensor
Faulty Phase 1 heat sink temperature sensor
Faulty battery charger temperature sensor
Battery fuse of BOOST 1 blown
Battery fuse of BOOST 2 blown
Battery fuse of BOOST 3 blown
DESCRIPTION
L1 bypass output locked
L2 bypass output locked
L3 bypass output locked
Pag. 94 di 246 + FR