Setup
Message
FULL ScALE =
inPUt =
ZErO
SPAn
LO AL =
Hi AL =
LEdS
rELAy
Aud
cErti
UnitS
Fact
PLAtE
Using the up and down arrow keys (), choose
ON or OFF. This option should always be set to OFF
unless you are using the TSI C
Calibrator. When ON is selected you can set the
measurement units as feet/min (FEEt) or m/s (Si)
using the up and down arrow keys (), and then
set a density correction factor using the up and down
arrow keys (). For a more detailed explanation
see section titled "More Detail on the C
Velocity Calibrator Option".
Full scale value: 0.1000 to 99990
Input signal: 0–5 VDC, 0–10 VDC, 1–5 VDC,
2–10 VDC, 0–20 mA, 4–20 mA
Zero adjust: ±1% of selected full scale value
Span adjust: 0.100 to 1.900
Low alarm: between –1 and full scale
High alarm: between 0 and full scale
LEDs: latched or unlatched
Relays: latched or unlatched
Audible alarm: on or off
When on, choose between latched and unlatched
®
C
function: on or off
ERTIFIER
FEEt (feet/minute) or Si (meters/second)
Density correction factor: 0.1000 to 1.9000
Plate choices: nOnE, 1, 2, tiny
ERTIFIER
Available Settings
–9–
®