Installation of Outdoor Unit

Installation of Outdoor Unit

1. Installation Locations

• If an awning is built over the unit to prevent
direct sunlight or rain exposure, make sure
that heat radiation from the condenser is not
restricted.
• Ensure that the spaces indicated by the
arrows around the front, back and side of the
unit are followed.
• Do not place animals and plants in the path of
the warm air.
• Take the air conditioner weight into account
and select a place where noise and vibration
are minimum.
• Be considerate of the surroundings when
choosing the location for the equipment to be
installed.
2. Piping length and the elevation
Model
Gas
MR24UY3J
Ø15.88(5/8)
MR36UY3J
Ø15.88(5/8)
If installed tube is shorter than 7.6 m, additional charging is not necessary.
Additional Refrigerant = (A -7.6) x Additional refrigerant (g)
6 Air Conditioner
Pipe Size
mm(inch)
Liquid
Standard
Ø9.52(3/8)
Ø9.52(3/8)
Indoor unit
A
B
Outdoor unit
More than
300(11 13/16)
F e
n c
o b
e o
s t a
c l e
Length A
Unit : m(ft)
Max.
7.6(25)
50(164)
7.6(25)
75(246)
A
Indoor unit
More than
More than
More than
300(11 13/16)
300(11 13/16)
300(11 13/16)
r
s
More than
700(27 9/16)
Unit : mm(inch)
Elevation B
Unit : m(ft)
Standard
Max.
5(16)
30(98)
5(16)
30(98)
Outdoor unit
B
More than
600(23 21/32)
Additional
refrigerant
Unit :
g/m(oz/ft)
40(0.43)
40(0.43)