Routine Maintenance; Filling The Machine Bottle - FLO-DYNAMICS CCST 288 Manual Del Usuario

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

ROUTINE MAINTENANCE

FILLING THE MACHINE BOTTLE

This operation must be performed whenever the available refrigerant fluid in the bottle is less
than 4lb 8 oz. (2kg) and must in any case be performed when the "empty bottle" alarm is
displayed. Procure a bottle of R134a and connect the liquid side coupling of the external bottle
to the high pressure hose (if the external bottle is not supplied with a liquid side coupling,
upend it to recover liquid refrigerant). Open the tap of the external bottle and the high-pressure
tap of the machine. If the external bottle is not supplied with a suction device, turn it upside
down to obtain the fastest delivery rate.
Switch the machine on. The MAIN MENU will appear after a few seconds:
Select NEXT MENU:
Select BOTTLE FILLING:
Set the quantity of refrigerant to be transferred to the machine bottle (the quantity must be
between the limit values suggested by the machine) and press START to confirm:
Press START again:
Press START again:
The machine will now fill the machine bottle with the preset quantity ±1,1lb (≈ 500g). When the
quantity minus 1,1lb (≈ 500g) is reached, the machine will stop and display:
INSTRUCTIONS MANUAL
AUTOMATIC PROCEDURE
ASSISTED PROCEDURE
<NEXT MENU>
Gas avail
X,XX lb
CALIBRATION
DATA AND CONFIGURAT.
SERVICE ALARM
BOTTLE FILLING
BOTTLE FILLING
Set amount
xx lb
Min: x
max: xx lb
Press START
Use the HP hose to
connect external
bottle and
press START.
Open the external
bottle tap, open
HP tap, and
press START.
FILLING BOTTLE
0 lb
-15-