Communication; Operation; Operation On Battery - MGE Pulsar ESV 8+ Manual De Instrucciones

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

communication

The communication port 9 , at the rear of
Pulsar, delivers information in the form of
an RS232 serial link supported by the com-
munication protocol exclusive to
MGE UPS SYSTEMS. The Solution-Pac
programs use the data made available by
this protocol.
RD TD
0V
1
5
4
3
2
9
8
7
6
I
1 - ground
2 - TD
3 - RD
V
5 - common
ESV Driver software (included in the
CD-ROM: EMB/ESVPLUS/CONFIG) lets
you edit the default parameter of Pulsar:
battery test frequency
(default: every week);
nominal output voltage
(default: 120 Volts);
high/low voltage thresholds
(defaut: 138/92 Volts);
Fader/Booster activation thresholds
(defaut : 102/128 Volts);
on/off conditions:
automatic restart,
forced reboot,
energy saving,
cold start.
MGE UPS SYSTEMS
option 1
status information card: after the card is
installed in the rear of the Pulsar, communi-
cation port 15 transmits status information
on a SUB-D 9-pin female connector using
the following pinouts:
1 - ground,
4 - normal operation,
5 - common,
7 - low battery warning,

9 - operation on battery.

9
0V
5
4
3
9
8
n.c.
n.o.
0V
Relay breaking capacity:
Vmax = 25V DC, Imax = 10mA
n.o. : normally open,
n.c. : normally closed.
Pulsar ESV 8+/11+/14+/22+ EB 22/EB 22XLA : 86-153277-00
option 2
SNMP card: after the card is installed in
the rear of the Pulsar, communication port
15 transmits information supported by the
SNMP protocol on an RJ45 or BNC
connector.
option 3
battery extension module Pulsar EB
22XLA (for Pulsar ESV 22+):
Switch off Pulsar ESV 22+ (push
button 3 ), disconnect the input
connection cord 5 .
Connect battery connection cord 19
(included with Pulsar EB 22XLA) to Pulsar
EB 22 and connect to Pulsar EB 22XLA.
2
1
You can connect 7 Pulsar EB 22XLA in
15
parallel.
7 6
Contact your retailer for further details.
n.o.
0V
13

Publicidad