Replacement Filter Cartridges; Filter Cartridge Replacement Procedure - Watts One Flow OFTWH Manual De Instalación, Operación Y Mantenimiento

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Operation
With sufficient pressure, operation of the Watts OneFlow
System is completely automatic. Dependable operation involves
only periodic filter changes and service documentation.
Maintenance
Routine maintenance of your OneFlow
filter cartridge changes and/or replacement of sump O-rings.
If the system sizing recommendations have been followed,
the OneFlow
Cartridge should last two years.
®
Filter Change Frequency
The filters should be changed in response to the following
conditions.
OFTWH-RM • 24 months since installation or last filter change.
3.
2.
System involves periodic
®
6.
8.
4.
®

Replacement Filter Cartridges

OneFlow
systems can only be used with OneFlow
®
cartridges. Use of replacement cartridges other than those
specified will void warranties, certifications and may compromise
equipment protection, water quality and equipment life.

Filter Cartridge Replacement Procedure

7.
IMPORTANT
Determine whether all equipment connected to the OneFlow
system must be turned off prior to shutting off water supply from
filters.
1. If required, turn off equipment.
2. Turn OFF water to OneFlow
Inlet Ball Valve.
3. Press the red button to release pressure.
4. Remove housing(s) - use filter wrench if necessary.
5. Clean inside of housing sumps with warm water. If desired,
disinfect housing using a teaspoon of household bleach.
Add to filter bowl and add water. Let stand 5 minutes and
discard.
6. Insert new cartridge into filter housing. Match cartridge
model number to model number on bracket.
7. Make certain the O-ring is properly positioned and reinstall
filter housing (hand tighten only). Check O-ring for damage
and replace if damaged or distorted.
8. Slightly open the inlet ball valve; push the red pressure relief
button to release trapped air until a small amount of water
comes out - release the red button and fully open the ball
valve.
9. Open the flush valve downline from the filter housing (if
equipped) and flush the new cartridge to drain or bucket
for two (2) minutes or until water runs clear. If no flush valve
is present, disconnect line from equipment to flush to drain.
NOTICE
10. With water supply inlet valve OPEN and water flow con-
firmed, turn on connected equipment. Failure to supply
water to equipment may cause serious damage.
11. Record filter change on the service log.
5
filter
®
system by closing
®
®

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Oftwh

Tabla de contenido