WARNING
Risk of Fire or Electric Shock
• Disconnect power at the circuit breaker(s) or disconnect switch(es) before installing or servicing.
• Installation and/or wiring must be in accordance with national and local electrical code requirements.
• Use wires rated at least 90°C - COPPER conductors ONLY.
• Replace plastic insulator covering terminals before powering ON.
• KEEP DOOR CLOSED AT ALL TIMES when not servicing.
NOTICE
• Rotate timer dial clockwise only.
• Do not move the clock hands on the timer. Moving the clock hands can damage the timer.
Load Ratings:
T101M/T103M/T106M:
40 A RESISTIVE, INDUCTIVE, TUNGSTEN
OR 1000 VA PILOT DUTY 120/208/240 VAC;
2 HP (24 FLA) - 120 VAC; 5 HP (28 FLA) - 240 VAC
16 A ELECTRONIC BALLAST, 277 VAC
T104M:
40 A RESISTIVE EACH POLE, 120-480 VAC
40 A INDUCTIVE, TUNGSTEN OR 1000 VA
PILOT DUTY EACH POLE 120V-277 VAC;
2 HP (24 FLA) - 120 VAC; 5 HP (28 FLA) - 240 VAC
16 A ELECTRONIC BALLAST, 277 VAC
Wiring Diagrams:
T101M: SINGLE POLE SINGLE THROW (SPST)
CLOCK MOTOR: 120 VAC, 60 HZ.
CLOCK MOTOR VOLTAGE AND CYCLE MUST BE AS SPECIFIED. TO
ORDER REPLACEMENT, INDICATE PART NO. (WG--) ON MOTOR COVER.
TIME
ON
DIAL
TRIPPER
TIME
POINTER
OFF
TRIPPER
MANUAL
LEVER
T103M: DOUBLE POLE SINGLE THROW (DPST)
CLOCK MOTOR: 120 VAC, 60 HZ.
CLOCK MOTOR VOLTAGE AND CYCLE MUST BE AS SPECIFIED. TO
ORDER REPLACEMENT, INDICATE PART NO. (WG--) ON MOTOR COVER.
TIME
ON
TRIPPER
DIAL
TIME
POINTER
OFF
TRIPPER
MANUAL
LEVER
Wiring Instructions: Remove 1/2 inch of insulation from wire ends. Tighten terminal screws firmly (2-18 in-lbs).
Use solid or stranded COPPER conductors only. May use two wires of the same size and type.
MAX.
MIN.
MINIMUM
75°C INSULATION MAX. MOTOR
INSUL-
COPPER
LOAD
LOAD (HP)
(AMP)
ATION
WIRE SIZE
3 PHASE
SINGLE PHASE
TEMP(°C)
(AWG)
120 V.
240 V.
208 V.
14
90
1/2
2
15
12
20
90
1
2 1/2
N/A
3
10
30
90
2
8
5
40
90
-
Programming Instructions:
1.
TO SET "ON" AND "OFF" TIMES: Hold trippers against edge of CLOCK-DIAL, pointing to time (AM or PM) when ON and OFF
operations are desired, tighten tripper screws firmly. For additional tripper pairs on CLOCK-DIAL order 156T1978A.
2.
TO SET TIME-OF-DAY: Pull CLOCK-DIAL outward. Turn in either direction and align the exact time-of-day on the CLOCK-DIAL
(the time now, when switch is being put into operation) to the pointer. DO NOT MOVE POINTER.
Operating Instructions:
TO OPERATE SWITCH MANUALLY: Move MANUAL LEVER below CLOCK-DIAL left or right as indicated by arrows. This will not
effect next operation.
IN CASE OF POWER FAILURE, reset CLOCK-DIAL to proper time-of-day. See programming instructions.
WIRING
DIAGRAM
GRD.
A
1
2
120V
NEUT.
SUPPLY
LINE
GROUND
TYPICAL
WIRING
DIAGRAM
A
1
2
3
4
120/240
NEUT.
VOLT
LINE 1
3 WIRE
SUPPLY
LINE 2
GROUND
GR.
PRESSURE PLATE
TERMINAL SCREW
240 V.
MAKE SURE WIRE
N/A
INSULATION CLEARS
PRESSURE PLATE
T100 SERIES MECHANISM INSTRUCTION SHEET
24 Hour Dial Time Switch Mechanisms
T104M: DOUBLE POLE SINGLE THROW (DPST)
CLOCK MOTOR: 208-277 VAC, 60 HZ.
CLOCK MOTOR VOLTAGE AND CYCLE MUST BE AS SPECIFIED. TO
ORDER REPLACEMENT, INDICATE PART NO. (WG--) ON MOTOR COVER.
TIME
CLOCK
DIAL
MOTOR
TIME
POINTER
OFF
TO
TRIPPER
LOAD
MANUAL
LEVER
T106M:
ONE NORMALLY OPEN, ONE NORMALLY CLOSED CONTACTS - (CAN BE WIRED AS SPDT)
CLOCK MOTOR VOLTAGE AND CYCLE MUST BE AS SPECIFIED. TO
ORDER REPLACEMENT, INDICATE PART NO. (WG--) ON MOTOR COVER.
CLOCK
DIAL
CLOCK
TIME
MOTOR
POINTER
OFF
TRIPPER
MANUAL
TO
LEVER
LOADS
WIRING INSTRUCTIONS: To wire switch follow diagram above. To wire as SINGLE POLE
NORMALLY CLOSED, move clock motor lead from terminal 3 to 1, and connect LINE to 1,
LOAD to 2. To wire as SINGLE POLE DOUBLE THROW, install jumper (the same gauge
as line wire) between 2 and 3 and connect LINE to 2, LOADS to 1 and 4. NOTE: Line 2 if
present is uninterrupted.
WIRING
DIAGRAM
ON
240 V 2 WIRE
TRIPPER
AND GROUND
A
GR
LINE 1
240V
LINE 2
SUPPLY
277/480 VOLT CONNECT MOTOR LEADS TO TERMINALS
"A" AND 1 AND SUPPLY NEUTRAL TO TERMINAL "A".
CLOCK MOTOR: 208-277 VAC, 60 HZ.
ON
TRIPPER
CLOCK
MOTOR
FROM
GRD
208V
A
240V
N
OR
277V
LINE
SUPPLY
FIGURE 1
TYPICAL WIRING SINGLE POLE NORMALLY OPEN
SEE WIRING INSTRUCTIONS BELOW FOR OTHER TYPES
CLOCK
MOTOR
1
2
3
4
TO
LOAD(S)
GROUND
WIRING DIAGRAM
1
2
3
4
TO
LOAD
GROUND

Publicidad

loading

Resumen de contenidos para Intermatic T100 Serie

  • Página 1 T100 SERIES MECHANISM INSTRUCTION SHEET 24 Hour Dial Time Switch Mechanisms WARNING Risk of Fire or Electric Shock • Disconnect power at the circuit breaker(s) or disconnect switch(es) before installing or servicing. • Installation and/or wiring must be in accordance with national and local electrical code requirements. •...
  • Página 2 FICHE D’INSTRUCTION DES MÉCANISMES SÉRIE T100 Mécanismes de minuterie à cadran 24 heures Risque d’incendie ou de choc électrique AVERTISSEMENT • Débrancher l’alimentation au niveau des disjoncteurs ou des sectionneurs avant de procéder à l’installation ou à l’entretien. • L’installation et/ou le câblage doivent être conformes aux exigences du code de l’électricité...
  • Página 3 HOJA DE INSTRUCCIONES DEL MECANISMO SERIE T100 Mecanismos de interruptor temporizador con dial de 24 horas ADVERTENCIA Riesgo de incendio o descarga eléctrica • Desconecte la energía desde los disyuntores o los interruptores de desconexión antes de realizar la instalación o el mantenimiento. •...
  • Página 4 INTERMATIC INCORPORATED Spring Grove, Illinois 60081-9698 U.S.A. www.intermatic.com 158--01661...

Este manual también es adecuado para:

T101mT103mT106mT104m