3.3.2 Panel installation

(1)
Align the panel with the unit body in the direction indicated by
the arrow (see Figure 3.14).
(2)
When mounting, secure the two fixed steel ropes on the unit
body to the hooks on the installation cover of the swing motor
on the panel (see Figure 3.14,
(3)
Connect the leads from the swing motor, and display box from
the panel to the corresponding connections on the unit body
respectively. Take care to use protective casing to wrap the
connection terminals, and use a reliable fixture to secure and
strengthen the safety isolation of the terminals.
(4)
Install and secure the panel on the unit body with bolts
0; DQG ZDVKHUV VHH )LJXUH 
installation cover of swing motor must sink into the
corresponding drain pan.
(5)
Adjust the four panel hook screws to keep the panel level, and
lift it evenly up to the ceiling.
(6)
Adjust the panel slightly in the direction indicated by the arrow
(see Figure 3.14, ), so that the centre of the panel aligns with
3
the centre of the opening of the ceiling. Verify that the hooks in
all four corners are securely in place.
Steel rope
1
Note: Please operate
according to the direction
of the arrow,or it can not be
disassembled when it is
necessary.
Steel rope
2
Swing motor installation cover
Figure 3.14
(6)
Continue to evenly tighten the screws under the hooks of the
panel until the foam thickness between the unit body and the
air outlet on the panel is reduced to about 4-6 mm, and there is
good contact between the panel and ceiling surface.
Panel sealing sponge 3
Panel
Panel foam 1
Air plate
Figure 3.15
and
).
1
2
4
 1RWH WKDW WKH
Drainage side
Guard of wire
(Protrusion 20mm)
Bolt, washer
4
Swing motor side
Inlet air
Body
Panel sealing
sponge 2
Ceiling
Panel sealing
sponge 1
Panel foam 2
Outlet air
Caution
7KH SODVWLF FRYHU SODWH SURWUXGLQJ IURP WKH VZLQJ PRWRU PXVW EH
embedded within the concave area of the sealing plate.
0DNH VXUH WKH ZLULQJ RI WKH VZLQJ PRWRU LV QRW FDXJKW LQVLGH WKH VHDOHG
foam.
$LU DQG ZDWHU OHDNDJHV PD\ UHVXOW LI WKH VFUHZV DUH WRR ORRVH 6HH
Figure 3.16.
1R JDS LV DOORZHG EHWZHHQ WKH FHLOLQJ DQG WKH SDQHO 6HH )LJXUH 
,I LW GRHV QRW DIIHFW WKH OLIWLQJ DQG ORZHULQJ RI WKH LQGRRU XQLW DQG WKH
water discharge piping, you can use the openings at the four corners of
the panel to adjust the height of the indoor unit. See Figure 3.18.
Leakage
Ceiling
Dew
Droplets of condensed water, dripping water.
Hexagon nut
Horizontal adjustment
Ceiling
Gaps are
not allowed
3
3.3.3 First hang the air inlet grille on the panel, and then connect
the leads of the swing motor and display box to the
corresponding connections on the unit body respectively. Use
the protective casing (accessories 3, 4) to enclose the
connecting terminals, and use tie straps (accessory 5) to fasten
securely to strengthen the safety isolation at the terminals. See
figures 3.19-3.21.
Unit
body
Panel
27
Figure 3.16
Figure 3.17
1. First loosen the nut
2. Adjust the nut
Figure 3.18
Lead at unit body
Lead at panel
Figure 3.19