Warning / Danger of electric shock
!
Hazardous voltages are present in certain parts of this electrical equipment during operation. Incorrect handling of the
equipment can result in death, severe personal injury or substantial property damage. Only qualified personnel are allowed to
work on or around this equipment. The successful and safe operation of this equipment is dependent upon proper transport,
storage and installation. Before installation or maintenance work is carried out, the main switch must be switched off and
locked to prevent it from being switched on again. If these rules are not adhered to, contact with live parts or improper use can
result in death or severe personal injury.
Important Note: Input 3 phase circuit breaker is required! (Refer to "Input Data")
Caution
The device may only be opened by qualified personnel. Electrostatically sensitive devices (ESD)
Description and construction
The SITOP 48V/10A power supply are built-in units. The relevant local regulations must be observed during installation.
Primary switched-mode power supplies for connection to a 400-500 V, 50/60 Hz three-phase AC system (TN-, TT- or IT-system acc. to
VDE 0100 T 300 / IEC 364-3); output voltage +48 V DC, potential-free, short-circuit resistant and stable under no-load conditions.
Technical specifications
6EP1456-2BA00
Input data
Input rated voltage V
:
in rated
400 to 500 V 3 AC, 50/60 Hz
Voltage range:
360 to 550 V 3 AC
Alternative: ??? to ??? V DC
Mains buffering time at 400 V :
7 ms
Input rated current I
:
in rated
1.1-0.9 A
Inrush current is limited to (25°C):
2
<18 A, <0.8 A
s
Required 3-ph. miniature circuit breaker:
6 to 16 A, characteristic C
Alternative:
circuit-breaker 3RV1021-1DA10, setting of
the thermal overcurrent trip: 3 A or
3RV1721-1DD10 (UL489 - Listed)
Efficiency at full load (typical):
ca.93%
Power input (active power):
520 W
Installation
Mounting on a DIN EN 50022-35x15/7.5 standard rail. To ensure adequate convection, the device must be installed vertically, with the input
and the output terminals at the bottom. Be sure to leave a minimum clearance of 50 mm above and below the device. The supply voltage (3-
ph. AC 400-500 V) must be connected in accordance with IEC 60364 and EN
above (miniature circuit-breaker or circuit-breaker) and the disconnecting device for isolating the power supply. A current-operated earth-
leakage circuit-breaker must not be the sole device used where protection against indirect contact is required. The same applies for the entire
system protected by a current-operated earth-leakage circuit-breaker.
Connections and terminal assignment
Terminals
Function
L1, L2, L3
Input voltage 3-ph. AC 400- 500 V
PE
Protective earth conductor
+, –
Output voltage DC 48 V
13, 14
Floating relay contact (make contact)
for output voltage V
SIEMENS AG ÖSTERREICH, 10.2007
Output data
Output rated voltage V
48 V DC ±1% (as delivered)
Setting range: 42 to 56 V, adjustable by
potentiometer on front of device (see page 2 for
position)
Derating at V
>48 V:
out
4% [I
]/ V [V
] (max. 480 W)
out
out
Ripple content of output voltage:
<150 mV
ripple
pp
<240 mV
spikes
pp
Output rated current I
10 A
Two power supplies of identical design may be
connected in parallel in order to improve the
performance.
Environmental conditions
Temperature:
Storage/transport: -25.to +85°C [-13 to +185°F]
Operating:
Humidity:
according to EN 60721 class 3K3; no
condensation
Natural convection should be allowed to form
Weight
1.2 kg [2.65 lb.]
Terminal range
0.2 to 4 mm
AWG 24 to 10
>38 V.
out
4/8
:
out rated
:
out rated
0 to +60°C [+32 to +140°F]
50178.
It is important to provide the protective device referred to
Remarks
2
Screw-type terminals. Use a screwdriver with a blade width of
4 mm.
Recommended tightening torque 1.2 Nm.
Protection and monitoring
functions
Current limitation (threshold value):
1.05 to 1.2 x I
out rated
Current limitation dynamic:
15 A for 5 s/min
Response to short circuit (output):
Constant current approx. 11 A
Signaling:
> ~38 V
Green LED: V
out
Signals:
Floating relay contact for V
out
contact rating DC 60 V/0.3 A
Standards and approbations
Degree of protection IP20 to IEC 529
Protection class 1
Safety to EN 60950: SELV
Safe electrical isolation met in accordance
with EN 60950 and EN 50178;
Transformer corresponds EN 61558-2-17
Emission to EN 61000-6-3;
RI suppression to EN 55022, limit curve B
Noise immunity to EN 61000-6-2,
EN 61000-4-2/-3/-4/-5/-6/-11
CE marking acc. to 2004/108/EG and
2006/95/EG
cULus (UL 508), File E197259
SITOP smart 48V/10A