10 JPC-01 User's manual
cycle is defined by the Start node and End node fields. By
limiting the range the scan takes less time to finish.
•
Default Speeds defines the baud rate used during the
node scan cycle and normal communication. With the box
ticked, the node scan is performed at 9600 bit/s; the speed
is then increased to the maximum. With the box unticked,
the speeds are defined by the Scan Speed and Comm
Speed fields respectively.
•
Leave the Default (247) and Default Speeds boxes ticked
(default) during the point-to-point connection (steps 1...3).
7. Check the COM port used from DriveStudio.
8. Untick the boxes Default (247) and Default Speeds in the
COM port used.
9. Change the setting of End node according to the maximum
number of nodes.
10. Change the setting of Scan Speed to 57600 bit/s.
11. Leave the setting of Comm Speed on 57600 bit/s.
8
12. Click OK.
13. Connect all drives to the RS-485 network.
14. Scan the network by selecting View – Refresh or restarting
DriveStudio.
15. DriveStudio will show all drives connected to the network.
9
8
10
11