INCLUDED:
(5) 1 x 4 Terminal Blocks
(2) 3.2 cm Stand offs
(4) Screws
(2) Nuts
(6) 3.9k Ohm
End of Line Resistors
Shipped on Board:
(2) Shunts
COMPATIBILITY REQUIREMENTS
To ensure proper operation, this module shall be connected to a
compatible system control panel. Contact System Sensor for a list
of compatible detectors. The CZ-6 Module shall be mounted in a
suitably grounded Metallic Cabinet for EMC compliance.
WIRING
NOTE:
All wiring must conform to applicable local codes,
ordinances, and regulations.
1.
Install module wiring in accordance with the job drawings and appropri-
ate wiring diagrams.
2.
All wiring to the CZ-6 is done via terminal blocks. In order to properly make
electrical connections strip approximately 5 mm of insulation from the end
of wire, sliding the bare end of the wire under the clamping plate screw.
3.
Set the address on the modules per the job drawing. Use the rotary code
switches to set the address of the first module (between 01 and 94).
FIGURE 1. INTERFACE TWO-WIRE CONVENTIONAL DETECTORS
1. To use a common power supply between multiple CZ-6 modules, connect
a long power supply jumper from T5 or T6 to T5 or T6 on the adjacent CZ-6
module.
CONNECT MODULES TO
LISTED COMPATIBLE
CONTROL PANELS ONLY
3.9K EOL
RESISTOR
(INCLUDED)
+
–
CLASS B IDC (TYPICAL)
POWER TO THE NEXT INTERFACE
MODULE MUST BE EXTERNALLY
SWITCHED TO RESET THE DETECTORS.
+
FROM PANEL OR
–
PREVIOUS DEVICE
+
–
TO NEXT DEVICE
COMMUNICATION LINE 32 VDC MAX.
TWISTED PAIR IS RECOMMENDED.
(3) Shunts
1) Long Power Supply Jumper
+
–
(+)
(–)
POWER-LIMITED
AND SUPERVISED
INSTALL DETECTORS PER MANUFACTURER'S INSTALLATION INSTRUCTIONS.
The remaining modules are automatically assigned to the next five higher
addresses. For example, if the base address switch is set to 28, the next five
modules will be addressed to 29, 30, 31, 32 and 33.
DO NOT set the lowest address above 94, as the other modules will be as-
signed to nonexistent addresses.
4.
A shunt is provided to disable a maximum of two unused modules. Mod-
ules are disabled from the highest address and work downward. If two
modules are disabled, the lowest four addresses will be functional, while
the highest two will be disabled. For example, if the shunt for Address
Disable is placed on "two" and the base switch is set to 28, the modules
will be assigned to 28, 29, 30 and 31 while disabling the highest two posi-
tions.
NOTE: Place unused shunts on single pin to store on board for future use.
WIRING NOTES
• All external power supplies must be power limited with battery
back-up.
BASE ADDRESS
6 7 8 9
5
4
3
2
1
0
A/B SELECT
A/B SELECT
DISABLE 1
DISABLE 2
2
6 7 8 9
5
4
3
2
1
0
STATUS
INDICATORS
C0199-00
I56-2256-009
2/28/2020