3. INITIAL CONFIGURATION PROCEDURE
The MasterAria is configured mainly from the "acqua" remote terminal.
Further settings are made using the dipswitches on the board inside the panel: HYCT000000.
Below are the various phases required to complete the configuration of MasterAria.
3.1
Dipswitch settings
The dipswitches on the MasterAria main board are used to select a number of predefined settings concerning the type of AHU and installation. This
configuration must then be completed by the settings made on the "acqua" terminal. Set the dipswitches as follows:
Dipswitch
Setting
1
ON=Enable heat/cool function enabled (probe B2 on coil). Probe B3 enabled only
when DIP1=ON and DIP4= ON;
OFF= Enable heat/cool function disabled
2
ON = Enable digital input 2 for heat/cool changeover
OFF= Disable digital input 2 for heat/cool changeover
3
ON = Remote off active
OFF= Remote off active not active
4
ON = AHU with 2 water coils
OFF= AHU with 1 water coil
5
ON = Electric heater fitted
OFF= Electric heater not fitted
6
ON = Control probe is the probe on the acqua terminal (BT)
OFF= Control probe selected between B1, B2 or B3 (correspondingly P15, P16 or P17
must be =5)
3.1.1
Accessing the configuration menu
To access the parameter configuration menu, with the unit off press the
The password entered using the
Code +050001260 – Rel. 2.0 – 22/01/08
RS485 serial board
Programming key with battery
Programming key with power supply
key adapter
Programming
NTC HP , JST connector , L= 1 m single pack
NTC HP, JST connector, L= 3 m single pack
NTC HP, JST connector, L= 5 m single pack
NTC HP, JST connector, L= 1 m pack of 50pz.
NTC HP, JST connector, L= 1,6 m pack of 50pz.
NTC HP, JST connector, L= 3 m pack of 50pz.
NTC HP, JST connector, L= 5 m pack of 50pz.
buttons is 22.
Note
for the implementation see parameter P56 :
0
1
Functions inhibited : ON/OFF timer, Sleep.
Automatic operation forced on
and
buttons.
16
MasterAria
N.C.=Heat, N.O.=Cool
N.C.= Cool, N.O.=Heat
Fig. 3.a