Fan operating mode
Configuration of the outlet limits
Freecooling and freeheating
configuration
3.2
Management of an electric heater
MasterAria can manage an electric heater with On-Off or proportional 0-10V control.
Proceed as follows:
4.
Move dipswitch 4 OFF, if a 0-10 V signal is used;
5.
Move dipswitch 5 ON;
6.
Press the
3.3
Management of a unit with a water coil only:
If this type of unit needs to be managed, the operation of the coil is established by the parameters relating to the proportional bands.
In any case, dipswitch 4 must be in the OFF position.
Coil model
Heating / cooling
Heating only
Cooling only
Code +050001260 – Rel. 2.0 – 22/01/08
P118
P106, P125, P126
P104, P105
button until the display shows the heater symbol.
Parameters
P115=xx / P116=xx
P115=0 / P116=xx
P115=xx / P116=0
0 = 3 speed
1 = minimum speed
2 = single speed (normally used for AHUs)
P106= minimum cooling/heating valve-heater outlet temperature
P125= maximum outlet limit
P126= differential on the outlet limits
P104= Freecooling activation delta
P105= Freeheating activation delta
Fig. 3.b
19