Dipswitch set up:
Eng
When CU4200 is used offline, the dipswitch setting has to be OFF for all 4 switches (0000).
When connected to an online CU420E by BUS485, the CU4200 dipswitch setting is used to give each device on the BUS485 a unique
address. Ensure that the address in the software is the same as the one you put on the hardware. (See Table). Both ends of the BUS485
must have the RS485 BUS termination resistor in the ON position, intermediate CU4200 need to have the resistor in OFF position.
Configuración del dipswitch:
Esp
Si la CU4200 está en modo offline, la configuración del dipswitch ha de estar en OFF con los 4 switches en off (0000).
Cuando la CU4200 está conectada a una CU420E ONLINE por BUS485, el dipswitch de la CU4200 se usa para asignarle una
dirección dentro del BUS485. Esta dirección ha de ser detallada en el software. Ver tabla adjunta. Ambos extremos del BUS485 han
de tener la resistencia del terminal en posición ON, y el resto de CU4200s han de tener este resistor en posición OFF.
DIP-Schalter Einstellungen:
Deu
Wenn die CU4200 im Offline Modus verwendet wird, müssen alle DIP Schalter auf "OFF" stehen.
Bei der Nutzung der CU4200 in Kombination mit einer CU42E0, muss jede CU4200 eine eindeutige ID haben. Die ID wird über die DIP-Schalter eingestellt und muss mit der Konfiguration in
der Software übereinstimmen. Für die Auswahl der korrekten Adresseinstellungen bitte die Abbildung nebenan beachten. Bei der ersten und letzen Komponente im Bus muss jeweils der
Abschlusswiderstand auf "ON" gesteckt werden.
Configuration du Dipswitch:
Fra
Si la CU4200 est en mode déconnectée, les réglages du dipswitch doit être éteint avec le 4 switches en OFF (0000).
Lorsque la CU4200 est connectée à une CU420E ONLINE par BUS485, le dipswitch de la CU4200 est utilisé pour attribuer une adresse dans le BUS485. Cette adresse doit être détaillé dans
le logiciel. Voir tableau ci-joint. les deux extrémités de BUS485 doivent avoir les résistances de fin de ligne en position ON, et le reste des CU4200 doivent avoir cette résistance hors tension.
Dipswitch setup:
Ned
Indien de CU4200 offline gebruikt word, moeten de dipswitch instellingen voor alle 4 knopjes 'UIT' staan (0000).
Wanneer deze verbonden is via een online CU420E d.m.v. een 485BUS, moet elke CU42000 een uniek adres d.m.v. dipswitch instelling hebben. Deze instelling moet gelijk zijn zoals in de
software is aangegeven. Zie tabel hiernaast. Bij begin en eind van de 485BUS moeten de eindweerstanden op de 'ON' positie staan. Een CU4200 of CU420E die tussen begin en eind van de
bus zijn geplaatst, moet de eindweerstand op 'OFF' staan.
Dipswitch set up:
Sve
När CU4200 används Offline måste alla 4 Dipswitcharna stå i läge OFF (0000).
När du är ansluter CU4200 till en online CU420E med BUS485,används dipswitch inställningen i CU4200 för att ge varje enhet på BUS485 anslutningen en unik adress . Denna adress
används i programvaran för att identifiera CUn i programvaran.(Se tabellen bredvid.) Båda ändarna av BUS485 anslutningen skall ha RS485 termineringen i läge ON, mellanliggande
CU4200 skall ha termineringen i läge OFF.
Set up example:
IP
Signaling:
Eng
The LEDs in the top layer of the CU show the state of the system:
LED name
ON
BUS485
TAMPER
IN1-IN6
READER
RL1-RL4
Señaletica:
Esp
Los LEDs en la parte superior de la CU mostran el estado del sistema:
Nombre del LED
ON
BUS485
TAMPER
IN1-IN6
READER
RL1-RL4
European view
All contents current at time of publication.
SALTO Systems S.L. reserves the right to change availability of any
item in this catalog, its design, construction, and/or materials.
Ned
Sve
1
Description
GREEN ON: the unit is powered correctly
BLINKING RED: the unit is not powered properly (check power supply)
BLINKING ORANGE: addressing mode
OFF: not powered
ON CU4200:The unit is communicating with the CU42E0
ON CU42E0: To be defined
OFF CU4200:The unit is not communicating with the CU42E0 (press the CLR to start detection process)
OFF CU42E0: To be defined
ON: tamper alarm active
OFF: tamper alarm not active
ON: active input (depends on the input type configured in the software)
OFF: inactive input (depends on the input type configured in the software)
ON: the reader is communicating with the CU
OFF: the reader is not communicating with the CU (press the CLR to start detection process)
ON: the relay is activated (NO is connected with C).
OFF: the relay is inactive (NC is connected with C).
Descripcióon
VERDE ON: el dispositivo está correctamente alimentado
ROJO INTERMITENTE: el dispositivo no está correctamente alimentada (comprobar la fuente de alimentación)
NARANJA INTERMITENTE: modo direccionamiento
OFF: sin alimentación
ON CU4200: El dispositivo se comunica con la CU42E0
ON CU42E0: Por definir.
OFF CU4200: el dispositivo no se comunica con la CU42E0 (presione el botón CLR para iniciar la detección)
OFF CU42E0: Por definir.
ON: alarma tamper activada
OFF: alarma tamper desactivada
ON: input activado (depende del tipo de input configurado a través del software)
OFF: input desactivado (depende del tipo de input configurado a través del software)
ON: el lector comunica con la CU
OFF: el lector no comunica con la CU (presione el botón CLR para iniciar la detección)
ON: relé activado (NO está conectado con C).
OFF: relé desactivado (NC está conectado con C).
Installatiehandleiding CU42xx
Installationsguide CU42xx
2
©
2015 SALTO Syst ems S.L.
1
2
3
0
0
0
0
0
0
0
0
1
0
0
1
0
1
0
Same configuration at SALTOs ProAccess SPACE Software
3
7/8
224901 -ED0 -01/09/2015
4
0
Offline
1
Address 1
0
Address 2
1
Address 3
0
Address 4
4

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Cu42e0Cu4200Cu42e0tCu42e0gCu4200tCu4200g

Tabla de contenido