Supply conditions
Mains connection
Power system
TT, TN
(with an earthed
neutral)
IT
Motor connection
Motors
Length of the motor
cable
Ambient conditions
Climatic
Storage
Transport
Operation
Site altitude
Pollution
Mechanical
Vibration resistance
Motor mounting
CDN40-xxx, DE/EN/FR/ES/IT
General data and operating conditions
Operation permitted without restrictions.
Implement the measure described for IT systems
(remove IT screw).
The machine/system manufacturer is responsible for
compliance with EMC requirements for noise
emission (EN 61800−3) for the machine/plant!
Operation with an integrated safety system is
not permissible.
EN 60034
Only use motors suitable for inverter operation.
Insulation resistance:
at least û 1.5 kV, at least du/dt 5 kV/ s
< 20 m (system cable, shielded)
IEC/EN 60721−3−1
1K3 (−30 ... +60 °C)
IEC/EN 60721−3−2
2K3 (−30 ... +75 °C)
IEC/EN 60721−3−3
Normal Duty:
3K3 (−30 ... +40 °C)
Operation at 4 kH.
Heavy Duty:
3K3 (-30 ... +55 °C)
Operation at 4 kHz: > +45 °C
Reduce the rated output current by 2.5 %/°C.
< 4000 m amsl
Above 1000 m amsl reduce the rated output current
by 5 %/ 1000 m.
IEC/EN 61800−5−1
Degree of pollution 2
2
(9.81 m/s
= 1 g)
Germanischer
General conditions: Acceleration resistant up to 2 g
Lloyd
IEC/EN 60721−3−3
3M6