Automatic detector
Indicator output
Minimum installation height
Maximum installation height
Minimum distance to lamps
Permissible operating temperature
Permissible rel. humidity
Permissible air speed
Protection class as per IEC 60529
Weight (without/with packaging)
Bosch Sicherheitssysteme GmbH
Open collector connects 0 V over 1.5 kΩ
through, max. 15 mA
Out of arm's reach
Minimum installation height recommended by
BOSCH: 2.70 m
16 m (heed local guidelines)
50 cm
FAP‑O 520(-P): -20 °C to +65 °C
FAP‑OC 520(-P): -10 °C to +50 °C
<95 % (non-condensing)
20 m/s
FAP‑O 520(-P): IP 53
FAP‑OC 520(-P): IP 33
FAP‑O 520(-P): 170 g/360 g
FAP‑OC 520(-P): 180 g/370 g
Installation manual
Technical Specifications | en
2019.11 | 5 | F.01U.002.682
9