Connection; Hardware Characteristics - WEG CCK-01 Guia De Instalacion

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Expansion Module of Relay Outputs CCK-01

4.3 CONNECTION

The accessory CCK-01 is connected to the inverter CFW70X via terminals. For the default
connection:
XC1:15 (CC70X) to XC1:1 (CCK-01).
XC1:14 (CC70X) to XC1:3 (CCK-01).
With this connection, the inverter DO5 output will be connected to relay K2 of the CCK-01
and its contacts will be available at connector XC3 (CCK-01).
XC1:13 (CC70X) to XC1:2 (CCK-01).
With this connection, the inverter DO4 output will be connected to relay K1 of the CCK-01
and its contacts will be available at connector XC2 (CCK-01).

5 HARDWARE CHARACTERISTICS

The accessory CCK-01 has two relay outputs with reversible contacts with capacity of 1 A / 250 V
for each contact. The minimum current for each contact is 100 mA.
The connectors present on the accessory can be seen in the figure below and in
page 11
and
Table 5.2 on page
10 CFW70X
Figure 4.3: Connection of the CCK-01 to the CFW70x
11.
Figure 5.1: Connectors of the CCK-01 module