Trac-Lites Single-Circuit Current Limiting End Feed/In-Line Feed Connector
INSTALLING CURRENT LIMITING
FEED CONNECTOR ON
PENDANT MOUNTED TRAC
1. Follow instructions included with the
pendant mounting kits.
2. Install CURRENT LIMITING CIRCUIT
BREAKER(S) into PLATE.
3. Attach wires per WIRING INSTRUCTIONS
below.
4. Slide TRAC onto FEED CONNECTOR
ensure (2) CONTACT BLADES insert into
the gap of the trac BUS BARS.
5. Tighten FEED CONNECTOR LOCKING
SCREW(S).
6. Fasten COVER taking caution to avoid
pinching any wires.
See OPERATING INSTRUCTIONS.
END FEED WIRING
INSTRUCTIONS RCLF11
1. Strip ground wire enough to wrap around
#8 screw. Wrap copper portion of ground
wire around the GREEN GROUND
TERMINAL between the screw and washer.
Clamp wire using screw.
Diagram 1 (End Feed)
Diagram 2 (In-Line Feed)
WARRANTY
Juno Lighting Group warrants that its products are free from defects in material and workmanship. Juno Lighting Group's obligation
is expressly limited to repair or replacement, without charge, at Juno Lighting Group's factory after prior written return authorization has been
granted. This warranty shall not apply to products which have been altered or repaired outside of Juno Lighting Group's factory. This warranty
is in lieu of all other warranties, expressed or implied, and without limiting the generality of the foregoing phrase, excludes any implied warranty
of merchantability. Also, there are no warranties which extend beyond the description of the product on the company's literature setting forth
terms of sale.
Product Services Phone (888) 387-2212
1300 South Wolf Road • Des Plaines, IL 60018 • Phone 800-323-5068 • www.junolightinggroup.com
INSTALLATION INSTRUCTIONS
For RCLF11 and RCLF21
2. Strip White neutral wire 7/16" and connect
to NEUTRAL TERMINAL (N) of FEED
CONNECTOR. Clamp wire using screw.
See schematic Diagram 1.
3. Strip HOT supply wire and connect to
CURRENT LIMITING CIRCUIT BREAKER
LINE Wire (supplied on current limiting
circuit breaker).
4. Connect LOAD wire from CURRENT
LIMITING CIRCUIT BREAKER (supplied on
current limiting circuit breaker) to trac
connector Terminal (P1).
IN-LINE FEED WIRING
INSTRUCTIONS RCLF21
1. Strip ground wire enough to wrap around
#8 screw. Wrap copper portion of ground
wire around the GREEN GROUND
TERMINAL between the screw and washer.
Clamp wire using screw.
2. Strip White neutral wire 7/16" and connect
to NEUTRAL TERMINAL (N) of FEED
CONNECTOR. Clamp wire using screw.
See schematic Diagram 2.
3. Strip HOT supply wire and connect to
CURRENT LIMITING CIRCUIT BREAKER
LINE Wire (supplied on current limiting
circuit breaker).
Diagram 3 (In-Line Feed)
Diagram 4 (In-Line Feed)
© 2009 Juno Lighting LLC
4. Connect LOAD wire from CURRENT
LIMITING CIRCUIT BREAKER (supplied on
current limiting circuit breaker) to trac
connector Terminal (P1).
5. Connect (P1) Terminal (connector 1) to (P1)
Terminal (connector 2).
6. Connect (N) Terminal (connector 1) to (N)
Terminal (connector 2).
7. Two current limiting circuit breakers can be
used for in-line applications. See schematic
Diagrams 3 & 4.
OPERATING INSTRUCTIONS
1. Place luminaires on trac. Switch CURRENT
LIMITING CIRCUIT BREAKER(S) to ON
position. Turn main power ON to supply
connector.
• The CURRENT LIMITING CIRCUIT
BREAKER(S) will automatically switch to OFF
if its ratings are exceeded. OFF is designated
by the visibility of a complementary color on the
CURRENT LIMITING CIRCUIT BREAKER(S).
• If CURRENT LIMITING CIRCUIT BREAKER(S)
will not remain on: reduce the wattage on the
trac so the total wattage is less than the wattage
specified on the CURRENT LIMITING CIRCUIT
BREAKER(S). Turn the CURRENT LIMITING
CIRCUIT BREAKER(S) to ON.