Connections; Operating Data; Electric Data - LEGRAND IME CONTO D6-Pd Manual Del Usario

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

Energy meter 100A
direct connection

5. CONNECTIONS

Wiring diagrams:
3
6
L1
L2
L3
L1
L2
L3
1
4
L1
L2
L3
N
Terminal board marking and diagram combination:
T1 / T2
RS485
E
SG
1
C
+
12 / 24V d.c.
INPUT
OUTPUT
E
1
C
12 / 24V d.c.
Max. 30V 50mA
T1 / T2
MBUS
E
1
C
A
B
12 / 24V d.c.
Technical data sheet: IDP000207EN_01
9
N
7
11
T1/T2 (INPUT)
1 C
Modbus RS485
+
MBUS
A B
Codes: CE6DJ0DTCL1
Model: CONTO D6-Pd

6. OPERATING DATA

6.1 ELECTRIC DATA

Currents:
- Starting current, I
- Min. current, I
: 500mA
min
- Transitional current, I
- Reference current, I
- Max. current, I
max
Rated voltage:
- Reference three-phase voltage: 3x230V∼ / 3x400V
Frequenza nominale:
- F
: 50Hz; 60Hz
n
- Permitted variation: 49...51Hz; 59...61Hz
Connectable section:
- Copper wires
- Voltage connection terminals (L1, L2, L3, N):
Rigid wire
Flexible wire
ATTENTION: for safety reasons, it is compulsory not to exceed 4
A/mm
as current density in the input terminals
2
- Neutral connection terminal (N):
Rigid wire
Flexible wire
SG
- Terminal blocks in the upper part of the meter (input, pulse output):
Rigid wire
Flexible wire
Necessary tools:
- Voltages connection terminals (L1, L2, L3): flat screwdriver 6 mm or
Pozidriv PZ2
- Neutral connection terminal (N): flat screwdriver 4 mm
- Terminal blocks in the upper part of the meter (input, pulse output):
flat screwdriver 2,5 mm.
Updated: -
: 40mA
st
: 1A
tr
: 10A
ref
: 100A
Without bush
1 x 4 ÷ 50 mm²
1 x 4 ÷ 35 mm²
1 x 4 ÷ 35 mm²
Without bush
1 x 4 ÷ 16 mm²
1 x 4 ÷ 16 mm²
Without bush
1 x 0,2 ÷ 1,5 mm²
1 x 0,2 ÷ 1 mm²
1 x 0,2 ÷ 1 mm²
Created: 02/04/2019
With bush
-
With bush
-
1 x 4 ÷ 16 mm²
With bush
-
2 | 7

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Ce6dj0dtcl1

Tabla de contenido