T2QuickNet
ENGLISH
General instructions
Please read the complete installation instruction carefully. At the appendix
you will find a commissioning report which has to be filled out by a recog-
nised installer for warranty purposes. Tyco Thermal Controls warrants the
heating mat for 12 years and, in case of any defect, repair the damaged
heating cable or offer you a new product. This warranty does not include
preparatory work, i.e. work involved in locating the failure and restoring the
floor. Pay attention to local circumstances, standards and regulations.
To ensure electrical safety earth leakage ciruit breakers RCD 30mA shall be
used. The floor heating system shall be installed with circuit breaker with
min. 3 mm contact distance to guarantee a safe disconnection of the sys-
tem. Not valid for thermostats with an internal switch. Tyco Thermal
Controls cannot be held responsible for any failures which are related to
neglecting the measurements as described in this manual. The commis-
sioning report and a lay-out of the mat installation should be sent to the rel-
evant address as noted on the final page of the commissioning report. A
copy of this commissioning report should be kept by the owner of the
house and be displayed on the distribution panel in order to comply with
national electrical regulations.
Installation instructions
T2QuickNet may not be cut to length, crossed or installed closer than the
spacing of cables pre-installed on the mat. T2QuickNet can be installed
under floor tiles or natural stone. The thermal resistance of the floor con-
struction above T2QuickNet should be as low as possible
(Max. 0,15 m
2
K/W). Do not step on the mats during installation. Avoid
sharp objects and incautious pouring of concrete/filler. No airgaps are
allowed in the concrete/filler. Also the heating mat should not be laid across
expansion joints. The joint between the heating cable and the connection
cable must be located in the filler (grout) and must not be pulled up into
the conduit. Handle the joint with care. i.e. do not bent or pull the joint.
Always pay attention to instructions for the floor covering adhesive.
T2QuickNet shall be installed in min. 5 mm of concrete/filler. Do not lay
heating cable in areas that might be damaged by drilling etc. or might be
covered by cupboards etc. It is not allowed to place T2QuickNet under a
heat source such as a stove etc. The subfloor should be clean, plain, stable
and rigid, without cracks, sharp objects or adhesion-reducing substances.
Cracks are to be filled out on beforehand with a casting resin. Big rough-
5