Technical Specifications; Disposal Of The Product - Carel pGD2 Folio De Instrucciones

Display grafi co per pco
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

Technical specifi cations
power supply:
rated power:
Use a class 2 safety transformer with a rating of least 15VA.
Power supply connections to the pGD2/3 ("PGD")
Observe the following rules:
• The power supply terminals on the PGD are called G and G0. The connection is made using 2-pin removable terminals.
Possible cross-section of the wires: 0.5 to 1.5 mm
• A dedicated 800 mAT fuse must be installed externally between the power supply and terminal G;
• If the transformer that supplies the pGD is the same that also supplies "pCO" devices, then terminal G0 on the pGD must be
connected to terminal G0 on the pCO;
Important:
if the secondary of the power supply transformers needs to be earthed, then terminal G0 must be earthed, both on
the pCO and the pGD.
Interfaces
RS485 serial for communication with pCO controllers, via 3-pin removable terminals. Use a shielded twisted pair cable,
AWG20-22, maximum length 200 m. The total length of the network must not exceed 500 m. The capacitance between the wires
must not exceed 90 pF/m.
Note: to reach the maximum length use a bus layout with branches that do not exceed 5 m.
Functional characteristics
protocols supported:
backlighting:
General characteristics
operating conditions:
storage conditions:
index of protection (IP)*:
dimensions (mm):
environmental pollution:
category of resistance to heat and fi re:
class and structure of the software:
duration of the backlighting lamp:
*: The front panel of the PGD2 and PGD3 for panel mounting (code PGD****F**) is compliant with IP40 index of protection.

Disposal of the product:

The product is made up of electronic, glass, metal and plastic parts. The product may also feature a CCFL lamp, which
may contain small quantities of mercury. All these parts should be disposed of according to the legislation in force.
CAREL reserves the right to modify the features of its products without prior notice.
24 Vac ±15%, 50/60 Hz or 30 Vdc ± 25%
10 W
2
;
pLAN protocol, "Point-Point" protocol (text mode only)
with two levels of brightness, "high" and "normal"
2
pGD
pGD
3
-10T70°C, 0 to 85% rH non-condensing
IP20
see Fig. 1
2
D
A
30,000 hours at 20 °C and "normal" brightness
: 0T50°C, 0 to 85% rH non-condensing
: 0T45°C, 0 to 85% rH non-condensing
14
+050001041 rel. 2.2 - 13.10.2008

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Pgd3

Tabla de contenido