2 - ABOUT THE NEGATIVE AIR PRESSURE MACHINE/AIR PURIFIER

OptiClean
uses highly efficient filters and a heavy duty, to remove contaminated air from the room. When ducting the unit, the resulting
negative air pressure, or "vacuum effect," helps limit the spread of air-based contaminants into surrounding areas. OptiClean
portable solution designed to help convert normal hospital rooms into Airborne Infectious Isolation Rooms (AIIR).
If negative pressure is not required, such as in an open-air temporary hospital, business or home, the machine can be used as an air
purifier pulling air in, removing many contaminants, and discharging cleaner air back into the room.
OptiClean
Negative Air Pressure Machine features:
- Long-life HEPA H13 (or H14 in option) filter according to EN 1822.
- Standard M5 / Coarse 70% pre-filter according to EN 779/ ISO EN 16890
- 3 available units :1000, 1800 & 2500 m
- Vertical design for smaller footprint
- Portable and adaptable to nearly any location
- Heavy duty locking casters for easy and smooth transport
- Red lighted indicator to alert user when filters are overloaded
- 2,5 meters long power cord (access from behind the unit)
- 230V single phase - 50 / 60Hz
- Galvanized steel, powder paint fully insulated cabinet
- Options:
• Exhaust transition plate Ø250 mm for round ducting
• Diffuser
• UV Lamp
During normal use, this unit is intended to operate under the following site conditions:
- Maximum altitude: 2000 m,
- Minimum and maximum storage temperature: -20°C/+65°C,
- Minimum and maximum operating temperature: 0°C/+40°C,
- Indoor return air maximum humidity level: 27°C DB (dry bulb) at 65% RH (Relative Humidity),
- Clean interior environment (no corrosive substances present).
The unit requires protection from any form of impact during use.
This unit is designed to operate in an overvoltage category II and pollution degree 2 environment, in accordance with IEC
standard 664. To ensure a pollution degree 2 environment, the unit must be protected from water and oil splashes, and the
dust allowed to settle on it must be limited.
NOTE: the unit must be used indoor only. Keep away from sources of moisture, heat, flames.
This unit is not designed for Atex areas.