Cat. No. OSF20-IUW
Rated: 120-347 VAC, 50/60 Hz
Fluorescent: 800 VA @ 120 VAC - Ballast
1200 VA @ 277 VAC - Ballast, 1500 VA @ 347 VAC - Ballast, 1/4 Hp @ 120 VAC
Operating Temperature: -40°F to 160°F.
Relative Humidity: 20% to 90% non-condensing.
WARNINGS & CAUTIONS:
• TO AVOID FIRE, SHOCK, OR DEATH: TURN OFF POWER at circuit breaker or fuse and test that power is off before installing, servicing or replacing fixture!
• Controlling a load in excess of the specified ratings will damage the unit and pose the risk of fire, electric shock, personal injury or death. Check your load ratings to determine the unit's suitability for your application.
• Sensor MUST BE installed directly in a luminaire.
• To be installed and/or used in accordance with appropriate electrical codes and regulations.
• If you are not sure about any part of these instructions, consult an electrician.
• Use this device with COPPER OR COPPER CLAD WIRE ONLY.
FEATURES
• Passive infrared detection technology.
• True Zero-Cross relay technology provides maximum contact life and compatibility with electronic ballasts ƚ.
• 360 degree lenses for field-of-view (included)
- Blue Lens = 8 - 25ft mounting height
- White Lens = 20 - 40ft mounting height
• Aisle covers: add included aisle mask to either lens option.
DESCRIPTION
Leviton's Outdoor Integral Fixture Occupancy Sensor, Catalog Number OSF20, is designed to be mounted directly
into a luminaire. The wiring and housing of the sensor is installed adjacent to the ballast and hidden from view
behind the reflector cover. Only the PIR detector dome lens and locking ring are visible on the exterior of the fixture.
The sensor is designed to be mounted in a fixture and in a downward facing orientation.
The occupancy sensor is designed to be used in wet indoor and outdoor applications; food processing plants,
nurseries, greenhouses, parking garages, industrial facilities, etc.
The occupancy sensor utilizes passive infrared (PIR) technology to detect motion within its field of view. The PIR
Occupancy Sensor uses a small semiconductor heat detector that resides behind a multi-zone optical lens. This
Fresnel lens establishes dozens of zones of detection. The Sensor is sensitive to the heat emitted by the human
body. In order to initially trigger the Sensor, the source of heat must move from one zone of detection to another. The
device is most effective in sensing motion across its field-of-view.
This will automatically turn the lights ON. When motion is no longer detected, the sensor will conclude that the space
is unoccupied. This will initiate the Delay Timer. If the delay timer expires and no motion is detected, the lights will
turn OFF. If motion is detected, delay timer will stop and lights will remain ON.
INSTALLATION
NOTE: The OSF20 is supplied with two lens covers. The 360 degree High Bay lens (white color) is installed at the factory
with the Low Bay lens (blue color) in the carton. Choose the correct lens for your fixture height location and add the aisle
mask if desiring to block detection outside of the aisle. The OSF20 Sensor mounts in a 1.5" knock out hole in the luminaire.
1. WARNING: TO AVOID FIRE, SHOCK, OR DEATH: TURN OFF POWER at circuit breaker or fuse and test that power
is off before installing, servicing or replacing fixture!
2. Remove the locking ring by turning counter clockwise and mount sensor into a 1.5" knock-out in the luminaire. Replace
and hand tighten the lock ring. Choose the correct lens for your fixture height location and add the aisle mask if desiring
to block detection outside of the aisle. To add the Aisle Mask line up the "dot" on the Aisle mask with the "dot" on
the lens assembly and turn to hold in place.
3. Connect wires per appropriate Wiring Diagram as follows:
Line Voltage (fig 2): BLACK lead to LINE (Hot); RED lead to LOAD; WHITE lead to LINE (Neutral). Twist circuit
conductors together and push firmly into the appropriate wire connector. Screw connector on clockwise making sure
that no bare wire shows below the connector.
Low Voltage (fig 3): RED lead to + 24 VDC; BLACK lead to - 24 VDC; BLUE lead to Power Pack control wire.
4. Restore power at circuit breaker or fuse.
NOTE: Allow approximately two minutes for charge-up. If the lights turn ON and the LED blinks when a hand is waved
in front of the lens, then the Sensor was installed properly. If the operation is different, refer to the Troubleshooting
Section. The Sensor is factory preset to work without any adjustments. If you desire to change the factory settings,
refer to the Settings section.
SETTINGS
Time-Delay: Settings should be determined during the installation period. This adjustment controls the amount
of time the lights stay ON after the last detected motion. You may select
settings varying from 30 seconds, 10 minutes, 20 minutes and 30
minutes.
Sensitivity: Settings should be determined during the installation period.
This adjustment controls the sensitivity of the passive infrared (PIR)
detection.
NOTE: After power is turned ON, allow two minutes for this unit to warm
up before performing Time-Delay settings.
TROUBLESHOOTING
• Lights will not turn ON
- Sensor is wired incorrectly: Confirm that the sensor's wiring is done correctly and inspect visually for problems.
- Lens is dirty or obstructed: Inspect the lens visually and clean if necessary, or remove the obstruction.
• Lights will not turn OFF
- Sensor is wired incorrectly: Confirm that the sensor's wiring is done correctly and inspect visually for problems.
- Sensitivity set improperly: Adjust the SENSITIVITY dial.
• Lights turn OFF and ON too quickly
- Sensitivity set improperly: Adjust the SENSITIVITY dial.
- Time delay set improperly: Adjust the TIME DELAY dial.
WIRING DIAGRAMS
Line Voltage
Fig. 2
Hot (Black)
Line
120-347 VAC
50/60 Hz
Neutral (White)
Low Voltage
Fig. 3
Hot (Black)
Line
120-277-347 VAC
50/60 Hz
Neutral (White)
FOR CANADA ONLY
For warranty information and/or product returns, residents of Canada should contact Leviton in writing at Leviton Manufacturing of Canada Ltd to the attention of the Quality Assurance Department, 165 Hymus Blvd, Pointe-Claire
(Quebec), Canada H9R 1E9 or by telephone at 1 800 405-5320.
Leviton warrants to the original consumer purchaser and not for the benefit of anyone else that this product at the time of its sale by Leviton is free of defects in materials and workmanship under normal and proper use for five years from the
purchase date. Leviton's only obligation is to correct such defects by repair or replacement, at its option. For details visit www.leviton.com or call 1-800-824-3005. This warranty excludes and there is disclaimed liability for labor for removal
of this product or reinstallation. This warranty is void if this product is installed improperly or in an improper environment, overloaded, misused, opened, abused, or altered in any manner, or is not used under normal operating conditions or not in
accordance with any labels or instructions. There are no other or implied warranties of any kind, including merchantability and fitness for a particular purpose, but if any implied warranty is required by the applicable jurisdiction, the duration
of any such implied warranty, including merchantability and fitness for a particular purpose, is limited to five years. Leviton is not liable for incidental, indirect, special, or consequential damages, including without limitation, damage
to, or loss of use of, any equipment, lost sales or profits or delay or failure to perform this warranty obligation. The remedies provided herein are the exclusive remedies under this warranty, whether based on contract, tort or otherwise.
© 2016 Leviton Mfg. Co., Inc.
OUTDOOR INTEGRAL FIXTURE
OCCUPANCY SENSOR
ƚ OSF20-IUW ONLY
SENSITIVITY
Fig. 1
OSF20-IUW
Black
Load
White
Red
Integral to Fixture
Red
Red
Black
Black
OSF20-ILW
Blue
Blue
Integral to Fixture
Power Pack
Load
Blue
Black
Blue
White
LIMITED 5 YEAR WARRANTY AND EXCLUSIONS
For Technical Assistance Call: 1-800-824-3005 (U.S.A. Only) www.leviton.com
Relative Humidity: 20% to 90% non-condensing.
INSTALLATION
COVERAGE AREA / AIRES COUVERTES / AREA DE COBERTURA
Fig. 4
High Bay Lens (White)
Lentille pour plafonds élevés (blanche)
Lente instalación en alto (blanca)
TOP
9.1m (30 ft)
6.1m (20 ft)
3m (10 ft)
0
3m (10 ft)
6.1m (20 ft)
9.1m (30 ft)
0
SIDE
6.1m (20 ft)
9.1m (30 ft)
12.2m (40 ft)
9.1m
6.1m
3m
(30 ft)
(20 ft)
(10 ft)
Fig. 6
High Bay Lens (White) with aisle mask
Lentille pour plafonds élevés (blanche), avec masque d'allée
Lente instalación en alto (blanca) con bloqueadores de pasadizo
9.1m (30 ft)
6.1m (20 ft)
3m (10 ft)
0
3m (10 ft)
10
20
6.1m (20 ft)
30
30
SEC
MIN
TIME
9.1m (30 ft)
0
S
H
E
6.1m (20 ft)
L
V
E
9.1m (30 ft)
S
12.2m (40 ft)
9.1m
6.1m
3m
(30 ft)
(20 ft)
(10 ft)
DIMENSIONS / DIMENSIONS / DIMENSIONES
Fig. 8
FRONT VIEW
VUE AVANT
VISTA FRONTAL
2"
[5.0 cm]
1.5"
[3.8 cm]
LED / DEL
LED
3.87"
[9.82 cm]
Detector / Détecteur
Detector
Cat. No. OSF20-ILW*
Input: 12-24 VDC, 20 mA
Operating Temperature: -40°F to 160°F.
*Requires the Leviton OPP20 power Pack
Fig. 5
Lentille pour plafonds réguliers (bleue)
Lente instalación en bajo (azul)
9.1m (30 ft)
6.1m (20 ft)
3.0m (10 ft)
0
3.0m (10 ft)
6.1m (20 ft)
9.1m (30 ft)
0
2.4m (8 ft)
6.1m (20 ft)
7.6m (25 ft)
0
3m
6.1m
9.1m
9.1m
(10 ft)
(20 ft)
(30 ft)
(30 ft)
Fig. 7
Changing Lens (adding aisle mask)
Remplacement de la lentille (et ajout du masque d'allée)
(añadiendo bloqueadores de pasadizo)
Tabs
Ergots
Pestañas
Notches
Encoches
Incisiones
S
H
E
L
V
E
S
0
3m
6.1m
9.1m
(10 ft)
(20 ft)
(30 ft)
SIDE VIEW
Gasket
VUE LATÉRALE
Joint
VISTA LATERAL
Empaquetadura
1.06"
[2.7 cm]
DI-000-OSF20-25B
AR0536
ENGLISH
Low Bay Lens (Blue)
0
6.1m
3.0m
3.0m
6.1m
9.1m
(20 ft)
(10 ft)
(10 ft)
(20 ft)
(30 ft)
Cambio de Lente
Aisle Mask
Masque d'allée
Bloqueadores
de pasadizo
Lens Cover
Lentille
Cubierta de lentes
Lock
Lens
Aisle
Ring
Cover
Mask
Anneau
Lentille
Masque
de blocage
Cubierta
d'allée
de lentes
Anillo
Bloqueadores
de seguro
de pasadizo
DI-000-OSF20-25B
AR0536

Publicidad

loading

Resumen de contenidos para Leviton OSF20-IUW

  • Página 1 Leviton warrants to the original consumer purchaser and not for the benefit of anyone else that this product at the time of its sale by Leviton is free of defects in materials and workmanship under normal and proper use for...
  • Página 2 DATOS DEL USUARIO NOMBRE: DIRECCION: PÓLIZA DE GARANTÍA: LEVITON S. de R.L. de C. V., LAGO TANA NO. 43 COL. HUICHAPAN, DEL. M. HIDALGO MÉXICO D. F., MÉXICO. CP 11290 Tel (55) 5082-1040. Garantiza este COL: C.P. producto por el término de un año en todas sus partes y mano de obra contra cualquier defecto de fabricación y funcionamiento a partir de la fecha de entrega o instalación del producto bajo las...

Este manual también es adecuado para:

Osf20-ilw