WIRING
NOTE: All wiring must conform to applicable local codes, ordinances, and
regulations.
1.
Install module wiring in accordance with the job drawings and appropri-
ate wiring diagrams.
2.
Make electrical connections by stripping approximately 5 mm of insula-
tion from the end of the wire sliding the bare end of the wire under the
clamping plate, and tightening the clamping plate screw.
3.
Set the address on the modules per the job drawing. Use the rotary code
switches to set the address of the module. (refer to Addresses section)
NOTE: In CLIP the remaining modules are automatically assigned to the next
five higher addresses. For example, if the base address switch is set to 28, the
next five modules will be addressed to 29, 30, 31, 32, and 33. DO NOT set the
lowest address above 94, as the other modules will be assigned to nonexistent
addresses.
FIGURE 1: WIRING AND PROGRAMMING ThE CR-6EA MODULE
RELAY CONNECTIONS
NC
NO
COMMON
SS-460-013
4.
A dip switch is provided to disable a maximum of four unused modules
in CLIP. Modules are disabled from the highest address and work down-
ward. If two modules are disabled, the lowest four addresses will be
functional, while the highest two will be disabled. For example, if the dip
switch is set to disable two addresses and the base address code wheel is
set to 28, the modules will be assigned to 28, 29, 30 and 31.
6.8"
2
6.8"
COMMUNICATION LINE
29 VDC MAX.
TWISTED PAIR
IS RECOMMENDED
FROM PANEL
OR PREVIOUS DEVICE
SYSTEM SENSOR
3825 OhIO AVE.
ST. ChARLES, IL 60174 USA
0843-CPD-0123
EN54-18:2005
INPUT/OUTPUT DEVICE
EN54-17: 2005
ShORT CIRCUIT ISOLATOR
CR-6EA
©2013 System Sensor
TO NEXT
DEVICE
C0205-03
13
I56-3920-001