INSTALLATION OF SENSORS Fig. 3
1. Disconnect Power.
2. Install CU series control unit(s) and, if applicable, AAR Add-A-Relay(s). See installation instructions for these products.
3. Run 3 conductor low voltage cable (18 to 22 AWG type CL2, CL2P, CL2PR, or CMR as appropriate) from control unit to sensor location(s) per wiring
diagram fig 3. Maximum cable length between power unit and farthest sensor is 250 feet (76 meters).
4. Confirm the correct coverage by simulating typical motion in the coverage area. To test the sensor, remove the access plate and press the TIMER TEST
MODE BUTTON fig 5. The lights will now turn off 8 seconds after motion stops. If the desired coverage is not achieved re-aim the sensor or relocate it.
After testing, push and hold the switch to return to the normal timer mode. Reinstall access cover and torque screw 10-12 lb-in (1.1 - 1.4 N-M). After
position of sensor is confirmed, torque pivot screws 10-12 lb-in (1.1 - 1.4 N-M).
ISOLATED RELAY Fig. 4
The isolated relay can be used to interface the sensor with an auxiliary system. Normally open and normally closed contacts are available. For normally
open contacts, utilize the yellow/white and blue/white wires. For normally closed contacts, utilize the black/white and blue/white wires.
Contact Rating (SPDT): 500ma @ 30VDC max.
AMBIENT LIGHT LEVEL CONTROL Fig 5
The sensor is factory preset to turn the lights on regardless of the daylight level. Setting the daylight level control will prevent the lights from turning on
when the daylight is above the set level. The daylight must be at the desired level to properly set this feature. To set the daylight level control:
1. Remove the access plate. Press the TIMER TEST MODE BUTTON to activate the 8 second test mode. Fig. 5
2. Adjust the photocell knob fully counter clockwise
3. Leave the sensor's coverage area. The lights should turn off after about 8 seconds. When the lights turn off, re-enter the area.
4. Slowly turn the photocell knob clockwise
level is above the set threshold.
5. Press and hold the timer test mode switch until lens flashes to return to the normal timer mode. Reinstall access cover and torque screw 10-12 lb-in
(1.1 - 1.4 N-M).
SENSOR CONTROLS & MODIFICATIONS
Hubbell Adaptive Technology sensors are designed to optimize performance by automatically adjusting the timing and sensitivity to meet the
application. The sensor controls can be modified for custom operation. The modification options are outlined below.
Timer test Mode
Push (momentary) for 8 sec timer
Push and hold (flash) for normal
operation
DIP Switch Position
OFF
A1
Automatic lights on
A2
A3
LED on (normal)
A4
Reset learned settings
Cat No. HAP1
FS BOX COVER
. This will keep the lights off regardless of the ambient light.
until the lights turn on. The sensor is now set to prevent the lights from turning on when the daylight
Adjustment Settings FIG. 5
ON
Manual lights on
Not Used
LED off
Toggle to reset
Cat No. HAP2
VJ BOX COVER
Daylight level (optional)
Max (clockwise): Off
Min (counterclockwise): lights never on
Infrared Sensitivity
Factory Setting: 75%
B3
B4
Mounting Accessories
Cat No. HAP3
NV BOX COVER
Primary Timer: Switches B1 & B2 –
controls time interval to turn off light(s)
after the space becomes unoccupied.
(Switch B3 must be set to ON)
Primary Timer (minutes)
4
8
B1
OFF
OFF
B2
ON
OFF
DIP Switch Position
OFF
Adaptive Time Out
Manual Time Out
Adaptive Sensitivity
Manual Sensitivity
Cat No. HAP4
½ NPT THREADED HUB
15
30
ON
ON
OFF
ON
ON