Installation Instructions
A.
Determine and mark the position of where the
Ducted unit is to be installed. Install the hardware
necessary to mount the threaded rods. Always
select a location strong enough to support the
entire weight.
B.
Install threaded rods to the hardware attached to
the structure.
C.
Lift the Ducted unit and position the threaded rods
into the four mounting foot on each corner.
D.
Using a level, adjust the readings on the threaded
rods to obtain level readings both side to side and
front to back.
10
Step 2 - Mounting the Unit
E.
Ream both inside and outside of the refrigerant
tubing where a cut has been made. Use every
precaution to ensure reamed copper chips not to
lodge inside the tubing.
Install the factory-supplied flare nuts on the
refrigerant tubing using an R-410A flaring tool
ONLY. Apply a small amount of refrigerant oil to
the back of the flare and threads.
Tighten the flares with a torque wrench and back-
up wrench to the specifications found in the outdoor
unit Installation Manual.
F.
Connect the grey flexible drain hose supplied
to the condensate pump discharge pipe. Tighten
the clamp securely. Using 3/4 " PVC, connect the
flexible hose to the building's condensate drain
system.
31-5000099 Rev. 1