9.2.
ALARMS & OPERATION HOLDING REGISTERS (READ/WRITE)
Name
Address
Alarm historic
0x20
Request_Word
0x21
Set Point
0x24
temperature
9.3.
COUNTERS & TEST HOLDING REGISTERS (READ ONLY)
We can read a list of counters that gather useful information, this info can help the installation to
better understand a hypothetical problem.
Name
Address
Start counter
0x30
Overheated
0x31
counter
Freezing risk
0x32
Total Operation
0x33
time
© ASTRALPOOL 2016 ALL RIGHTS RESERVED. PROPRIETARY DOCUMENT
Initial
Information
value
0
Contains information on alarms that have been activated
at some point. Must be reset by writing a 0 from the
MODBUS or removing electrical supply. Each bit has a
meaning associated with a type of alarm.
Bit
Alarm
0
1
Overheating alarm
2
3
Flow not present and needed
4
5
6
7
8
9
10
11
12
13
14
Freezing risk
15
8
It is the register that allows us to turn on or off the
heater. By default, the heater is off.
bit 0 Not used.
bit 1
1= °C
0=°F
bit 8
Manual On / Off
1: Turns heater on
0: Turns heater off
20
Temperature set point for water. Invalid values return a
type 4 exception.
Initial
Information
value
0
Number of times the heater has received power supply.
0
Every time there is an overheating alarm this counter
increases. When desired, it can be put to 0.
0
Every time there is a freezing risk alarm, this counter
increases. When desired, it can be put to 0.
0
Every hour of heating time, increases the counter by 1.
.
20