DANGER
!
Hazardous voltage.
Will cause death or serious injury.
Turn off and lock out all power supplying
this device before working on this device.
Not Vented
[ No Ventilados ]
NPG_ _ _
HPG_ _ _
LPG_ _ _
NPX_ _ _
HPX_ _ _
LPX_ _ _
Vented
[ Ventilados]
NPY_ _ _
HPY_ _ _
LPY_ _ _
Protect per UL 50
or equivalent
[Proteger
conforme a UL 50
o norma
equivalente]
64.5 in² MIN.
14 / 15
PELIGRO
!
Tensión peligrosa.
Puede causar la muerte o lesiones graves.
Desconectar la alimentación eléctrica antes
de trabajar en el equipo.
PG
32.0 MIN.
[ 81 cm ]
70.0 MIN.
[ 178 cm ]
20.0 MIN.
[ 51 cm ]
PG
32.0 MIN.
[ 81 cm ]
90.0 MIN.
[ 229 cm ]
28.0 MIN.
[ 71 cm ]
DANGER
!
Tension électrique.
Danger de mort ou risque de blessures graves.
Mettre hors tension avant d'intervenir sur
l'appareil.
Suitable for continuous operation at 100% of rating only if
used in a ventilated enclosure or cubicle space 90 by 32 by
28 in MIN. with Strap Kit Adapter, SSBPH .
Ventilated openings to be 64.5 square inches MIN. at the
top and bottom of enclosure. Openings should be located
at least 8 inches from the ends of the breaker.
Adecuado para operación continua a 100% de la capacidad;
solamente si se instala en un compartimento ventilado de
por lo menos 90 x 32 x 28 pulgadas (minimo); con el juego
de sujeción SSBPH. El compartimento debe tener dos
aberturas de 64.5 pulgadas cuadradas (minimo); una en la
parte inferior y otra en la parte superior. Estas aberturas
deben estar localizadas por lo menos a 8 pulgadas de los
extremos del interruptor.
Bestell-Nr. / Order No.:3ZW1012-0VL00-3AA0