JP1=
Jumper for selecting "STARTING" motor function:
1) Closed: starting function enabled
2) Open: Starting function disabled.
Dip-switch functions
N.B.:
Every change of functions have to be done without electricity.
DSW1= This selects the type of functioning of the P.P. button and Remote control.
Off= "OPEN" - "STOP" - "CLOSE" functioning
On= "OPEN" - "CLOSE" - "OPEN" functioning.
DSW2= This enables or disables the pre-blinking function (4 sec.).
Off= Pre-blinking disabled.
On= Pre-blinking enabled.
DSW3= With this Dip-Switch the electric lock (1.5 sec) + recoil is enabled or inhibited.
Off= Electric lock + recoil are inhibited
On= Electric lock + recoil are enabled
DSW4= It selects the type of intervention of the "Photocell FTCC" input in the opening phase.
Off= No intervention
On= Temporary stop
DSW5= This enables or disables the automatic re-closing with the time set using the "TCA TRIMMER"
Off= Automatic re-closing enabled.
On= Automatic re-closing disabled.
DSW6= It enables or inhibits the multiple-user function for blocks of flats of the "P.P. push-button" and
the Remote control.
Off= Multiple-user function inhibited
On= Multiple-user function enabled
Trimmer functions
TCA= This allows the automatic re-closing time to be adjusted when this is enabled by positioning the
DSW5 Dip-switch on OFF.
Adjustment can be from a minimum of 7 to a maximum of 160 seconds.
The minimum time is obtained by rotating the trimmer completely clockwise.
TL=
This allows the working time of the automation to be adjusted. The software protection will inter-
vene after this time has elapsed.
Adjustment can be from a minimum of 6 to a maximum of 90 seconds.
The minimum time is obtained by rotating the trimmer completely clockwise.
TRAC= This allows the gate leaf closing delay to be adjusted.
Adjustment can be from a minimum of 1 to a maximum of 15 seconds.
The minimum time is obtained by rotating the trimmer completely clockwise.
7