Descargar Imprimir esta página

Cooper Crouse-Hinds N2S Serie Información De Instalación Y Mantenimiento página 2

Publicidad

Idiomas disponibles

Idiomas disponibles

Figure3
Field Wiring Diagram
Transformer Volts
Source Voltage Range
220-110
220-240V, 50-60 Hz
440-110
440-480V, 50-60 Hz
550-110
550-600V, 50-60 Hz
Note: N2S Series uses Sylvania 120 MB, 3 Watt and
N2SU Series use factory sealed 120V LED lamps.
7.
Test wiring for correctness with continuity checks and
also for unwanted grounds with an insulation resistance
tester.
CAUTION
To prevent damage to enclosure, make sure that the
cover gasket and body flanges are free of any foreign
substances before mating to ensure proper gasket
sealing.
8.
Carefully assemble cover assembly to the device body
with the cover screws. Check the tightness of the
cover screws to ensure that the cover assembly is
securely fastened.
Do Not exceed 35 in. lb. of torque.
PILOT LAMP REPLACEMENT
N2S Series: incandescent, miniature bayonet base 120
VAC (Sylvania 120 MB Series)
N2SU Series: because the N2PLU pilot light assembly is
factory sealed, the LED lamp cannot be replaced. The
complete pilot light assembly will need to be replaced.
WARNING
To prevent electrical shock, be sure all power is turned
OFF before replacing the lamp or opening enclosure.
MAINTENANCE
1.
Frequent inspection should be made. The environment
and frequency of use should determine a schedule for
maintenance checks. It is recommended that it should
be at least once a year.
2.
Perform visual, electrical and mechanical checks on all
components on a regular basis.
Visually check for undue heating evidenced by
discoloration of wires or other components,
damaged or worn parts or leakage evidenced
by water or corrosion in the interior.
Electrically check to make sure that all connections
are clean and tight, and that contacts in the
components make or break as required.
Mechanically check that all parts are properly
assembled, and that operating mechanisms
move freely.
IF 703 • 4/05
Copyright
PUSHBUTTON, SELECTOR SWITCH
DEVICE AND PILOT LIGHT ASSEMBLY
REPLACEMENT
WARNING
To prevent electrical shock, be sure all power is turned
OFF before and during installation and maintenance.
Pilot Light Lamp Only
N2S Series: incandescent, miniature bayonet base 120
VAC (Sylvania 120 MB Series)
N2SU Series: LED, T3- 1 /4 miniature bayonet base 120
VAC, factory sealed.
Unscrewing the jewel makes replacement of the
incandescent pilot light lamp easy. It is not necessary to
remove the cover. Because the N2PLU pilot light assembly
is factory sealed, the LED lamp cannot be replaced. The
complete pilot light assembly will need to be replaced.
Install replacement pushbutton, pilot light or selector switch
following installation information supplied with each device.
The following lists the Crouse-Hinds replacement catalog
number.
N2S Pilot Light Device with Jewel
Pilot Light
Primary Power Source
Voltage Range
N2PL10*
120V, 50-60 Hz
N2PL20*
220-240V, 50-60 Hz
N2PL40*
440-480V, 50-60 Hz
N2PL50*
550-600V, 50-60 Hz
N2SU Pilot Light Device with Jewel
Pilot Light
Primary Power Source Transformer
Voltage Range
N2PLU10*-LED
120V, 50-60 Hz
N2PLU20*-LED
220-240V, 50-60 Hz
*Specify Jewel Color for each Pilot Light:
Color:
Red
Green
Amber
Symbol:
J1
J3
J6
N2PS and N2SW Series Replacement Contact Block:
ESWP126
ELECTRICAL RATINGS
Pilot Lights:
120-600 VAC
Selector Switches and
A600, Heavy Duty 10A at
Pushbutton Stations:
600 VAC
2005, Cooper Industries, Inc.
©
Transformer
Volts
—-
220/110
440/110
550/110
Volts
220/110
Clear
Blue
J10
J11
All statements, technical information and recommendations contained herein are based on information and tests we believe to be
reliable.The accuracy or completeness thereof are not guaranteed. In accordance with Crouse-Hinds "Terms and Conditions of Sale",
and since conditions of use are outside our control, the purchaser should determine the suitability of the product for his intended use
and assumes all risk and liability whatsoever in connection therewith.
Page 3
Cooper Industries Inc.
Crouse-Hinds Division
PO Box 4999, Syracuse, New York 13221 • U.S.A.
Copyright
©
2005, Cooper Industries, Inc.
IF 703
Revision 5
Revised 4/05
Supercedes 03/03

Publicidad

loading

Este manual también es adecuado para:

N2su serie