Fault/ cause/ remedy

Fault
Indicator lamp in the fitting
flashes
No flushing
Water flowing continuously
Undesired flushing
Flow volume too low
Flow volume too high
For latest prices and delivery to your door visit MyTub Ltd - www.mytub.co.uk - info@mytub.co.uk
Cause
• Battery voltage too low
• Water supply interrupted
• Battery voltage too low
• Filter in solenoid valve blocked
• Plug-in connector without contact
• The detection zone of the sensor system
is set too low/too high
• Solenoid valve defective
• Electronics faulty
• Solenoid valve defective
• The detection zone of the sensor system
is set too high
• Flow volume set too low
• Filter in solenoid valve blocked
• Solenoid valve defective
• Flow volume set too high
• Solenoid valve defective
Remedy
- Replace battery,
see Replacing battery
- Open isolating valve
in wall connection box
- Replace battery,
see Replacing battery
- Clean or replace filter,
see Cleaning or replacing filter
- Attach plug-in connector
- Increase/reduce detection zone using
remote control
(special accessories 36 206)
- Replace solenoid valve,
see Replacing solenoid valve
- Replace electronics,
see Replacing the top plate
with electronics
- Replace solenoid valve,
see Replacing solenoid valve
- An opposite object will be detected.
Reduce detection zone using remote
control (special accessories 36 206).
- Adjust flow volume,
see Setting the flow volume
- Clean or replace filter,
see Cleaning or replacing filter
- Replace solenoid valve,
see Replacing solenoid valve
- Adjust flow volume,
see Setting the flow volume
- Replace solenoid valve,
see Replacing solenoid valve
6