STAND BY (STOP)
MENU TREE
LANGUAGE SELECTION
Push and quickly release CAL button and then pressing + and – buttons select the language
choice. Push CAL to enter the language submenu and select "Language English" by pressing +
or - .
Push CAL to confirm the choice and ESC to go back in measuring.
DELAY START
LEVEL CONTROL
Rev 1.0
Push and hold the ESC/SBY button for 2 seconds during the functioning to put the
pump in stand by mode:
1) It stops dosing
2) Green on led blinks.
3) The display shows the measure of mA input on the second row and on the first
row it shows alternativenly the writing "Stop " and the value of flow rate % :
"Man.xx%" (for Manual functioning) and "Off xxx%" (for mA functioning) ; see
figure on the left side.
Push again the ESC/SBY button for 2 seconds to return the pump to the
programmed functioning.
WHAT IS IT? The delay start is the time in seconds (0-999sec) after the power on that the
pump waits before dosing the chemical product. During this period of time the display shows the
message "Delay" on the first row. The second row shows the value of mA input (see figure on the
left side). During the delay start the pump can't dose but it is possible to enter the menu and
modify the parameters and calibrations.
DELAY START EDITING
Push and quickly release CAL button and scroll the menu using + and –
buttons till the display shows "Delay Start". Push CAL to enter the submenu
and then by pressing + and – button choice the value in seconds (0-999).
Push CAL to confirm and ESC to go back in measuring.
The closing of the level input contact, free of tension, while the pump is
working, will cause:
1) the dosing stops
2) the green ON led blinks
3) The display shows the measure of mA input on the second row and on the
first row it shows alternativenly the writing "Level " and the value of flow rate
% : "Man.xx%" (for Manual functioning) and "Off xxx%" (for mA functioning)
; see figure on the left side.
When the level contact gets opened again, the pump returns to working mode
compatible with the actual inputs.
Push and quickly release CAL button during the
functioning to enter into the programming menu.
Push + or - button to navigate through the menu.
Push the CAL button to enter the submenus.
Cod. 00.008.647
8