Figure 2 CURB FOR ROOF
Figure 5
MODEL
A
VTR1000Q 10" Dia. 10" Dia. 10-3/4
VTR1400Q 10" Dia. 10" Dia. 10-3/4
VTR600R
8" Dia.
NOTE: The unit must be sealed between the roof (or
wall) and the underside of the flange with roofing mastic
to prevent leaks. For installation on a flat roof, or roofs
with a pitch less than 1-1/2" in 12", install ventilator on
the curb as shown in Fig. 2. Position the curb on flat roofs
so that the discharge (low) end points away from
prevailing wind.
3. Connect ventilator to the exhaust system with 8 inch
dia. duct for VTR600R and 10" dia. duct for VTR1000Q
and VTR1400Q. Use adjustable elbow to adjust to roof
angle. Tape all joints to prevent air leaks.
4. Connect ducting in the inlet to the ventilator with duct
tape.
5. Clearance to combustible material is 0".
II. FOR
WIRING
THERMADOR® PRODUCTS, USE INSTALLA-
TION INSTRUCTIONS PROVIDED WITH
THAT PRODUCT.
Figure 3
TYPICAL INSTALLATION USING THERMADOR HOODS
B
C
10-1/4
10-1/4
8" Dia.
10-3/8
11-1/2
TO
ALL
APPROVED
Figure 6 – Remote Blower Dimensions
D
E
F
3-1/8
17-5/8
3-1/8
17-5/8
4-5/8
14-7/8
III. WIRING TO A WALL MOUNT 4 POSITION
VENTILATOR SPEED CONTROL SWITCH:
1. Use Thermador 4 position ventilator speed control
model CTR3Q (purchased separately).
2. Power supply required for these ventilators is
15 amps. @120V. AC, 60 Hz. connected per local
codes.
3. Run three (3) #14 AWG. wires (black, white and
green) from the power supply at the electrical
circuit panel to the wall box. See Figure 8.
4. Run electrical conduit per local code to conduit
outlet in bottom of ventilator as shown in Fig. 5.
Other end of conduit will connect to wall box with
4 position switch. See Figure 8.
5. Run five (5) #14 AWG. wires in conduit between
Ventilator J-box and 4 position switch. Use color
coded wire corresponding to colors shown in
Figure 8.
6. Use spring type wire nuts (# 189692) supplied to
connect wires per Fig. 8 wiring diagram. (Lost or
missing wire nuts should only be replaced with:
spring type wire nuts, rated for a minimum of (2)
#18ga wires and maximum of (4) #14ga wires, UL &
CSA rated to 600V and 302 deg. F./150 deg. C.)
2
Figure 4
G
H
I
10-3/4
10
26-1/4
10-3/4
10
26-1/4
8-3/4
8
24
J
4
4
3-1/2