Installation Instructions - Bradley S19-460EFW Instalación

Manguera rociadora de mano con lavador de ojos/rostro para montaje sobre mostrador
Ocultar thumbs Ver también para S19-460EFW:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Installation
Installation
Step 1: Prepare deck for
installation
NOTE: Make sure that, when mounted,
the eye wash unit will measure 33-45
inches from the top of the sprayheads
to the finished floor. For usage as an
eye/face wash, the top of the
sprayheads of the S19-630 must be
33–45 inches from where the user
stands per ANSI Z358.1. The unit must
also be placed a minimum of 6" away
from the nearest wall or obstruction.
1. Rough-in 1/2" IPS supply piping
from wall where drench hose is
desired (piping supplied by
installer).
2. Select desired location in deck for
drench hose and drill a 1-5/16"
(34mm) diameter hole.
3. Install the drain plug using the
washers and locknut provided (see
Figure 2 and the parts list, page 4).
Step 2: Assemble eye/face
body wash unit
1. Assemble the component parts as
shown in Figure 2 on page 4.
• Be sure to apply pipe sealant to
all pipe joints.
Step 3: Connect water supply
1. Connect the water supply to the
unit (piping supplied by installer).
2. Mount the safety sign to the wall
using the sign-mounting hardware
supplied by installer.
3. Open the water supply line. Test
for leaks and adequate water flow.
Bradley Corporation • 215-1165 Rev. N; EN 07-516
5-1/4"
(133mm)
12-1/4"
(311mm)
33-45"
(838-1143mm)
TO FINISHED
FLOOR
Figure 1
7/2/07
S19-460EFW
6" (152mm) MININUM
DISTANCE FROM WALL OR
NEAREST OBSTRUCTION
3

Publicidad

Tabla de contenido
loading

Tabla de contenido