14. Technical Specifications

Application
Resistance measurement
method
Operation frequency
Resistivity measurement
method
Voltmeter
Measurement ranges
Accuracy
Earth resistance measuring of simple or complex
:
electrode
systems,
measurements
(Four
principle), and Spurious voltage according to IEC
61557-5
The
equipment
:
generated current in the soil, and measures, with
high precision, both that current and the voltage
developed in the soil by means of that current
flowing through grounding diffusion resistance.
The display shows the Resistance value.
270 Hz (resistance or resistivity measurement)
:
570 Hz, 870 Hz, 1170 Hz or 1470 Hz (resistance
measurement)
Max. variation: ± 1 Hz (both cases).
:
The equipment injects the current in the soil
though the external rods, and measures, with
high precision, both that current and the voltage
developed in the soil. The operator should inform
the distance between spikes and the equipment
automatically computes soil resistivity. The
display shows resistivity value, computed with
Wenner full equation.
In the voltmeter function, the equipment operates
:
as a voltmeter, making it possible to measure
voltages generated by parasitic currents.
Resistance: 0 - 20 kΩ (auto ranging)
:
Resistivity: 0 - 50 kΩm (auto ranging)
Voltage: 0 - 60 V
Resistance and Resistivity measurements:
:
R ≤ 2 kΩ: ± (2% of the measured value ± 2
digits)
R > 2 kΩ: ± (5% of the measured value ± 2
digits)
Voltage measurement:
± (3% of the measured value ±2 digits)
26
Ground
resistivity
terminal
Wenner's
injects
an
electronically

Hide quick links: