Important; Installation Instructions - Bradley S19-260 Instalación

Ocultar thumbs Ver también para S19-260:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Installation
Installation
NOTE: Flush the water supply line before
beginning installation.
Supplies Required:
• Supply piping to 1/2" NPT water supply inlet
• Drain piping to 1-1/4" NPT
• Tailpiece and trap to conform to local codes
• Sign-mounting hardware
Step 1: Prepare deck
1. Select the desired location for the eyewash
on the deck and make the necessary cutouts
per the rough-ins (see Figure 1).
Step 2: Install eyewash
IMPORTANT: To ensure proper operation,
the handle assembly should be in the
"up" position while the ball valve is
closed. To make the adjustment, rotate
the handle assembly 180° and reattach
to the ball valve.
1. Assemble the valve and pipe as shown in
Figure 2 on page 4 and connect it to the
bowl.
2. Lower the complete assembly through the
cutout and secure it to the deck with the
mounting hardware provided.
3. Attach the eye/face wash to the bowl.
4. Install the operating rod mechanism through
the hole provided.
5. Attach the operating lever to the valve and
secure.
Step 3: Connect water supply
1. Connect the water supply piping to the 1/2"
NPT inlet on the unit (piping supplied by
installer).
2. Connect the drain piping to the 1-1/4" NPT
drain outlet on the unit (piping supplied by installer).
3. Mount the safety sign to a wall using sign-mounting hardware (supplied by installer).
4. Open the water supply lines. Test for leaks and adequate water flow.
Bradley Corporation • 215-770 Rev. J; EN 07-508
12-7/8" (327mm)
13-5/8"
(346mm)
3-7/8"
(98mm)
Deck
7-3/4"
(197mm)
Figure 1
10/3/07
S19-260
1"
(25mm)
7/8"
(22mm)
9-1/4"
(235mm)
11-1/2"
(292mm)
6"
(152mm)
3