DIGITAL FANCOIL THERMOSTAT
Applications
System switch on cool mode: To achieve for energy saving, 1 hour after sleeping mode setting, set point
o
o
temperature will raise 1
C automatically, and 2 hours later, setting point temperature will raise 2
C and
keep on with this temperature until timer off, which is 8 hours. After timer off, set point will be restored
to formal setting automatically.
System switch on heat mode: To achieve for energy saving, 0.5 hour after sleeping mode setting, set point
o
o
temperature will decrease 1
C automatically, and1 hour later, setting point temperature will decrease 2
C,
o
2 hours later, setting will decrease 3
C and keep on with this temperature until timer off, which is 8 hours.
After timer off, set point will be restored to formal setting automatically.
Internal sensor or external sensor model option
If connect external sensor, the thermostat control temperature and display temperature will work with
external sampling; If select internal sensor, the thermostat control temperature and display temperature
will work with the internal sampling.
Room card function
When a room card function is activated (see configuration parameters), without the room card signal the
icon flashes and the set point temperature back to implicit parameters for cooling or heating. When it has
room signal it returns to the original state.
Window contact function
When a window card function is activated (see configuration parameters), without the window card signal
it will stop all the output on; only display the room temperature and valve or fan operating situation. The
mode is ventilation and flashes mode. When it has window card signal then return to the original state.
When the room card and window card without input signal at the same time, then the window card func-
tion is losing efficacy.
30 / 34