KTFD-01
DIGITAL FANCOIL THERMOSTAT
8. Select energy saving setpoint for cooling
o
This feature allows you to set energy saving setpoint temperature for cooling. The default setting is 25
C, it
o
o
can be changed between 25
Cto 30
C.
9. Room Card function mode option
This feature allows you to select the way to activate the energy saving mode.
Select OC to activate the energy mode by open circuit.
Select SC to activate the energy mode by close circuit.
Select 00 to cancel the energy mode.
10. Window Card function mode option
This feature allows you to select the way to activate the energy saving mode.
Select OC to activate the energy mode by open circuit.
Select SC to activate the energy mode by close circuit.
Select 00 to cancel the energy mode.
Factory default values
Switch off the thermostat, Press button ④ over 4 seconds till power on again means you have entered the
menu, long press button ④ over 4 seconds after "dEF" blinking readout three times, it means return to
factory default. (Caution: Please don't operate before malfunction happened.)
This function can help operator to recovery system when fault happened, display out of order or system
halted. Please use a pin to insert in button
hole till sounded click, then loosen it. Switch on thermostat
and observe it, if there still have troubles, please don't hesitate to contact with local agency for warranty