Connecting the temperature gauge using cable set F:
a.
b.
7.
Connecting a further AMC-Device (here, as an example, an
AMC2-16I-16O-EXT):
a.
b.
NOTICE!
i
Connect readers and contacts in accordance with the AMC2
installation guide (Order-No.: F.01U.028.714).
DANGER!
Before connecting the power supply, remove the fuse on the 3-
pole connector (1)!
Do not replace the fuse until the connection process has been
completed.
8.
Connecting the power supply:
a.
b.
c.
CAUTION!
Trim the external power cables such that the earth wire (yellow/
!
green) is at least 2cm (8/10") longer than the live wire (brown).
This will ensure that, if the wires are accidentally pulled, that
the voltage carrying wires will be disconnected first.
9.
Mount the mounting plate in the 19" rack using the G1
screws and the G2 cage nuts.
F.01U.097.256 | V 1.1 | 2008.12
Connect the B2a plug (black) to the negative terminal
of the second battery.
The ends B3a and B3b remain unused. Due to the pre-
mounted connector no further insulation is necessary.
Connect the 2-pole plug F1 to the socket marked RTH
on the PBC-60 power supply.
Fix the cable with cable tie D to the fastener E, in such
a way that the temperature gauge F2 is located close
to the batteries.
Connect the RS485 slave interface of the second AMC
device to the RS485 slave interface of the AMC2
marked RS-485EXT.
Connect the data lines (pins 3 and 6) as well as the
power lines (pins 1 and 2).
Clamp the neutral wire (blue) in the left screw
terminal marked N on the mounting plate.
Clamp the live wire (brown) in the right hand terminal
marked L1.
Attach the earth wire (yellow/green) to the mounting
plate with the screw to the left of the clip.