14
en
Connecting devices
Connecting an additional AMC device:
-
Connect the RS485 slave interface of the second AMC
device to the RS485 slave interface of the AMC2 marked
RS-485EXT.
You can provide each device with an individual power supply, or
pass power through from one device to the next:
-
If a second device receives its power supply from a first,
then please connect the power lines (pin 1 and pin 2) as
well as the data lines (pin 3 and pin 6).
NOTICE!
In general:
-
If the devices have their own power supplies then the
cable shielding should be grounded at one end only. The
i
loose end should be insulated to prevent any inadvertent
contact.
-
If one device passes power through to another, then the
cable shielding should be grounded at both ends.
CAUTION!
!
Do not create any ground loops.
NOTICE!
i
When connecting devices please consult the instructions and
notices in their respective installation manual.