Descargar Imprimir esta página

GE Interlogix RB404 Guia De Instalacion Y Configuración página 2

Publicidad

Idiomas disponibles

Idiomas disponibles

NK706/FEC406, NK708/FP408, NK712/FP412 and NK716/FP416
allow for up to four modules to be installed.
Connecting the master module
For RB404 connection see figure
For SB404 connection see figure
C
(SB404)
ONFIGURATION
If the SB404 module is configured as a sounder output, the short-
circuit and open-circuit faults are indicated on the fire panel with
the indicators for the sounder outputs. These outputs function then
in the same way as the sounder outputs of the main board and will
follow the actions when the Sounder and Silence Sounder buttons
are pressed.
If the SB404 module is configured as supervised 24 VDC output,
then the short-circuit and open-circuit faults are indicated by the
general fault indicator and can be reset only with the Reset button.
DIP switch configuration
DIP switch 8 on the SB404 is used to set the function of the
supervised output module (see Figure 5):
DIP switch 8 ON
24 VDC supervised output module
DIP switch 8 OFF
Sounder output module
Figure 5: SB404 DIP switch 8.
SB404 configured as 24 VDC
supervised output module.
In the RB404 DIP switch 8 is not used and should remain in the
OFF position.
C
(RB404/SB404)
ONFIGURATION
DIP switches 1 to 7 are used to configure the master module
relays (DIP switch 8 is used only to set the function of the
supervised output module on the SB404 - see previous section).
Programming options are:
Assignment of one relay per zone (correlative).
Assignment of 2 or 4 relays per zone.
Assignment of a single relay depending on combined events
in different zones.
Assignment of relays based on general events
Assignment of relays based on extinguishing outputs
See Table 1 for DIP switch address settings.
Assignment of one relay per zone (correlative)
This may be achieved in two different ways:
Setting the module address as 00.
Setting the address 01 to module 1 (so zone 1 is linked to
relay 1, zone 2 to relay 2 etc.), the address 02 to module 2
(so zone 5 is linked to relay 5, zone 6 to relay 6 etc.), the
address 03 to module 3 and the address 04 to module 4
Assignment of 2 or 4 relays per zone
Use the following DIP switch addresses to assign relay behaviour.
Address
08
09
10
11
.
.
SB404 configured as sounder
output module.
Zone
Relay
1
1 + 2
2
3 + 4
3
1 + 2
4
3 + 4
5
1 + 2
6
3 + 4
7
1 + 2
12
13
14
15
16
17
18
19
20
21
22
23
Assignment of a single relay depending on combined events
in differing zones
The event of each zone can be combined through Boolean
operations AND / OR, e.g:
Event zone 1 OR Event zone 2
these two events is true.
Event zone 1 AND Event zone 2
when both of these two events are true.
Address
32
33
34
35
36
37
Assignment of relays based on general events:
Address
40
41
42
43
2
8
9
10
11
12
13
14
15
16
1
2
3
4
5
6
7
8
The relay is activated if either of
The relay is activated only
Zone
1 OR 2
3 OR 4
5 OR 6
7 OR 8
9 OR 10
11 OR 12
13 OR 14
15 OR 16
1 + 2
3 + 4
5 + 6
7 + 8
9 + 10
11 + 12
13 + 14
15 + 16
1 OR 2 OR 3 OR 4
5 OR 6 OR 7 OR 8
9 OR 10 OR 11 OR 12
13 OR 14 OR 15 OR 16
1 + 2 + 3 + 4
5 + 6 + 7 + 8
9 + 10 + 11 + 12
13 + 14 + 15 + 16
Event
Alarm
Fault
Alarm
Fault
Alarm
Fault
Mute
Reset
3 + 4
1 + 2
3 + 4
1 + 2
3 + 4
1 + 2
3 + 4
1 + 2
3 + 4
ALL
ALL
ALL
ALL
ALL
ALL
ALL
ALL
Relay
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
Relay
ALL
ALL
1 + 2
3 + 4
1
2
3
4

Publicidad

loading

Este manual también es adecuado para:

Interlogix sb404