Eikon
Arké
20534
19534
Actuator with changeover relay output 16 A - 230 V.
CHARACTERISTICS.
• Rated supply voltage: BUS 29 V
• Input: 10 mA
• Changeover relay output
• Controllable loads at 120-230 V~ (contact NO):
- resistive loads: 6 A (20.000 cycles)
- incandescent lamps:
6 A (20.000 cycles)
- fluorescent lamps and energy saving lamps: 1 A (20.000 cycles)
- electronic transformers: 4 A (20.000 cycles)
- ferromagnetic transformers: 6 A (20.000 cycles)
• Controllable loads at 120-230 V~ (contacts NO and NC):
- motors cos ø 0.6: 3,5 A (100.000 cycles)
• Terminals:
- TP bus
- relay contacts (NC, C, NO)
• Consist with:
- By-me flush and surface mounting control units, rel.2.0 and next.
- By-me 2-module control units, rel. 2.0 and next.
CONFIGURATION.
FOR THE OPERATIONS OF INSTALLATION AND CONFIGURATION, SEE
THE By-me SYSTEM INSTRUCTIONS MANUAL.
• Functional blocks: 1
• Selecting the functional block (configuration): during group creation, when the
control unit requires pressing the device button:
- press the button, the LED will light up;
- with the LED on, the control unit will configure the functional block; at the end of
this operation the LED will go out.
PARAMETERS.
• one- or two-position stable operation;
• on delay and off delay: a value between 0 and 200 gives the time in seconds,
a value between 201 and 250 gives the time in minutes (for example 201 = 1
minute, 202 = 2 minutes, etc.);
One-position stable operation.
On delay: delay in closing the NO contact of the relay from receiving the close
command.
Off delay: time for which the relay has the NO contact closed.
Two-position stable operation.
On delay: delay in closing the NO contact of the relay from receiving the ON com-
mand.
Off delay: delay in opening the NO contact of the relay from receiving the OFF
command.
Note.
If a group is created with a number of relays in one-position stable mode, set for
all the same on and off delays and do not insert any other types of actuator in the
same group; in this way, it is possible to have the status of the one-position stable
relay indicated on the control button. For special requirements it is possible to use
the group depth (for example to switch on two-position stable relays or dimmers
with a single button).
• Default parameters: relay set on two-position stable operation with null on and off
delay.
SCENARIOS
The actuator can belong to multiple scenarios and, for each one of them, save the
status to retrieve when activating the scenario. For further details see the control
panel manual.
49400474B0 03 1909
Idea
Plana
16974
14534
FRONT VIEW.
Arké
Eikon
A
B
A B
Idea
Plana
A
B
A B
Caption:
A: led
B: configuration button
FIGURE 1.
ON delay
ON delay
ON
Control
ON
ON delay
OFF delay
Control
Control
ON
OFF
INSTALLATION RULES.
Installation should be carried out by qualified staff in compliance with the current
regulations regarding the installation of electrical equipment in the country where
the products are installed. The feeding circuit of the relay output must be protected
against overloads by a device, fuse or automatic circuit breaker, with rated current
not higher than 10 A. For further instructions, please see the manual attached to the
control panel.
CONFORMITY.
LV directive. EMC directive.Standard EN 50428.
REACH (EU) Regulation no. 1907/2006 – Art.33. The product may contain traces
of lead.
WEEE - Information for users
If the crossed-out bin symbol appears on the equipment or packaging, this means the product must
not be included with other general waste at the end of its working life. The user must take the worn
product to a sorted waste center, or return it to the retailer when purchasing a new one. Products
for disposal can be consigned free of charge (without any new purchase obligation) to retailers with
a sales area of at least 400 m
, if they measure less than 25 cm. An efficient sorted waste collection
2
for the environmentally friendly disposal of the used device, or its subsequent recycling, helps avoid
the potential negative effects on the environment and people's health, and encourages the re-use
and/or recycling of the construction materials.
BACK VIEW.
NO
C
NC
Terminals
bus TP
MONOSTABLE
OFF
BISTABLE
Viale Vicenza, 14
36063 Marostica VI - Italy
www.vimar.com